R3-NC2

P.  / 7

EM-842 Rev.8

CC-Link INTERFACE MODULE

(CC-Link Ver.1.10; for 32-point analog signals)

MODEL

R3-NC2

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If  you  have  any  problems  or  questions  with  the  product, 
please contact M-System’s Sales Office or representatives.

 PACKAGE INCLUDES:

  Network interface module ............................................ (1)
  Terminating resistor (110Ω, 0.25W) ............................ (1) 

 MODEL NO.

Confirm  Model  No.  marking  on  the  product  to  be  exactly 
what you ordered.

 INSTRUCTION MANUAL

This  manual  describes  necessary  points  of  caution  when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 CONFORMITY WITH EC DIRECTIVES

• The  equipment  must  be  mounted  inside  the  instrument 

panel of a metal enclosure.

• The actual installation environments such as panel con-

figurations,  connected  devices  and  connected  wires  may 
affect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure CE conformity.

 POWER INPUT RATINGS

Operational range & power consumption: Check the power 
rating for the unit on the specification label.
    Rating 100 – 120V AC: 85 – 132V, 47 – 66 Hz, approx. 20VA
    Rating 200 – 240V AC: 170 – 264V, 47 – 66 Hz, approx. 20VA
    Rating 24V DC: 24V  ±10%, approx. 12W

 UNPLUGGING THE MODULE

Before  you  remove  the  module  from  its  base  or  mount  it, 
turn off the power supply for safety.

 ENVIRONMENT

• Indoor use
• When heavy dust or metal particles are present in the air, 

install the unit inside proper housing with sufficient ven-
tilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C     

(14 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 WIRING

• Do  not  install  cables  (power  supply,  input  and  output) 

close  to  noise  sources  (relay  drive  cable,  high  frequency 
line, etc.).

• Do  not  bind  these  cables  together  with  those  in  which 

noises are present.  Do not install them in the same duct.

 AND ....

The  unit  is  designed  to  function  as  soon  as  power  is  sup-
plied, however, a warm up for 10 minutes is required for sat-
isfying complete performance described in the data sheet.

INSTALLATION

Use  the  Installation  Base  Model  R3-BSx,  or  Model  R3-
BSWx for free I/O address capability.

Before  mounting  the  Network  Interface  Module  onto  the 
Base, be sure to configure the module as explained below.

 DATA ALLOCATION

The setting determines the data area size assigned to each 
I/O module mounted on the base.
The data sent/received via CC-Link is mapped according to 
this setting.
See “COMPONENT IDENTIFICATION”.

 NODE ADDRESS & BAUD RATE

See “COMPONENT IDENTIFICATION”.

 NETWORK SLOTS ON THE BASE

With Model R3-BSx base, mount the I/O Modules from the 
left end (I/O 1) to the right in order that the Network Mod-
ule assigns data areas from I/O 1.
Network  Module(s)  and  Power  Module  are  mounted  basi-
cally  at  the  right  end  though  technically  they  could  be 
mounted in any position.

With Model R3-BSWx base, there is no limitation in mount-
ing positions as I/O address can be assigned freely to each 
module using rotary switches equipped on the base.

I/O 1

I/O 2

I/O n

Summary of Contents for R3-NC2

Page 1: ...metal particles are present in the air install the unit inside proper housing with sufficient ven tilation Do not install the unit where it is subjected to continuous vibration Do not subject the uni...

Page 2: ...SW2 ON 8 7 6 5 4 3 2 1 SW3 ON 4 3 2 1 ON 8 7 6 5 4 3 2 1 SW1 Functions 1 2 3 4 5 6 Terminal Block Configuration Jack 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 FG SLD DG DB DA Node A...

Page 3: ...re size 0 75 1 25 mm2 3 2 13 dia 4 min 16 12 47 max 6 max 24 3 12 max COMMUNICATON CABLE CONNECTIONS DA DB DG SLD FG MASTER UNIT DA DB DG SLD FG R3 NC2 DA DB DG SLD FG I O UNIT TERMINATOR blue white y...

Page 4: ...ATA The figure below shows the allocation of the data sent from the network module to the master INPUT DATA The figure below shows the allocation of the data sent from the master to the network module...

Page 5: ...US4 out of 10 to 110 the other types out of 15 to 115 sta tus for each module The bit corresponding to such modules turns to 1 RX n 3 through RX n 6 are unused RX n 8 through RX n 14 are unused RX n 7...

Page 6: ...TA models R3 RS4 TS4 and US4 16 bit binary data With C temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature unit the integer section of raw data is...

Page 7: ...L INCIDENTAL OR SPECIAL DAMAGES OF ANY KIND WHATSOEVER M System Co Ltd 5 2 55 Minamitsumori Nishinari ku Osaka 557 0063 JAPAN Phone 06 6659 8201 Fax 06 6659 8510 E mail info m system co jp PARAMETERS...

Reviews: