background image

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-5659  Rev.6  P. 1 / 8

INSTRUCTION MANUAL

CONTACT OUTPUT MODULE

(32 points)

MODEL

R1M-D1

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

This product is for use in general industrial environments, 
therefore may not be suitable for applications which require 
higher level of safety (e.g. safety or accident prevention sys-
tems) or of reliability (e.g. vehicle control or combustion con-
trol systems).

For safety, installation and maintenance of this product 
must be conducted by qualified personnel.

 

PACKAGE INCLUDES:

Remote I/O module .............................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.
For detailed information on Modbus supported functions, 
refer to Modbus Protocol Reference Guide (EM-5650).
The R1M is programmable using the PC configurator soft-
ware.  For detailed information on the PC configuration, 
refer to the R1CON instruction manual.  The R1CON PC 
Configurator Software is downloadable at M-System’s web 
site: http://www.m-system.co.jp.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• 

This equipment is suitable for Pollution Degree 2 and  In-
stallation Category II (transient voltage 2500V).  Rein-
forced insulation (RS-232-C/RS-485 or output to power: 
300V) and basic insulation (RS-232-C/RS-485 to output: 
300V) are maintained.  Prior to installation, check that 
the insulation class of this unit satisfies the system re-
quirements.

• 

Altitude up to 2000 meters.

• 

The equipment must be mounted inside a panel.

• 

Insert noise filters.  Okaya Electric Industries Model 
SUP-E1H or equivalent for the power source connected to 
the unit, and TDK Model ZCAT 3035-1330 or equivalent 
for the RS-232-C cable are recommended.

• 

The equipment must be installed such that appropriate 
clearance and creepage distances are maintained to con-
form to CE requirements.  Failure to observe these re-
quirements may invalidate the CE conformance.

• 

The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

• 

Install lightning surge protectors for those wires connect-
ed to remote locations.

 

POWER INPUT RATING & OPERATIONAL RANGE

• 

Locate the power input rating marked on the product and 
confirm its operational range as indicated below:

  100 – 240V AC rating: 85 – 264V, 47 – 66 Hz, approx. 10VA
  24V DC rating: 24V ±10%, approx. 7W

 

GENERAL PRECAUTIONS

• 

Before you remove the module, turn off the power supply 
and output signal for safety.

 

ENVIRONMENT

• 

Indoor use.

• 

When heavy dust or metal particles are present in the air, 
install the module inside proper housing with sufficient 
ventilation.

• 

Do not install the module where it is subjected to continu-
ous vibration.  Do not subject the unit to physical impact.

• 

Environmental temperature must be within -5 to +60°C     
(23 to 140°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

• 

Be sure that the ventilation slits are not covered with ca-
bles, etc.

 

WIRING

• 

Wrong connection may damage the module.

• 

Do not connect cables to moving parts or pull them tightly.

• 

Do not install cables close to noise sources (relay drive 
cable, high frequency line, etc.).

• 

Do not bind these cables together with those in which 
noises are present.  Do not install them in the same duct.

 

AND ....

• 

The module is designed to function as soon as power is 
supplied, however, a warm up for 10 minutes is required 
for satisfying complete performance described in the data 
sheet.

Summary of Contents for R1M-D1

Page 1: ...Okaya Electric Industries Model SUP E1H or equivalent for the power source connected to the unit and TDK Model ZCAT 3035 1330 or equivalent for the RS 232 C cable are recommended The equipment must be...

Page 2: ...fer to EXTERNAL DIMENSIONS TERMINAL CONNECTIONS Connect the module referring to the connection diagram EXTERNAL DIMENSIONS unit mm inch M3 SCREW TERMINALS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18...

Page 3: ...2 1 10 12 11 13 15 14 16 17 18 20 19 21 22 23 24 25 27 26 28 29 30 31 32 33 35 34 36 ch 1 ch 2 ch 3 ch 4 ch 5 ch 6 ch 7 ch 8 COM ch 9 ch 10 ch 11 ch 12 ch 13 ch 14 ch 15 ch 16 COM ch 17 ch 18 ch 19 ch...

Page 4: ...able wire size 0 75 to 1 25 mm2 AWG19 16 Recommended manufacturer Japan Solderless Terminal MFG Co Ltd Nichifu Co ltd 6 max 24 3 12 max 3 2 13 dia mm inch EURO TYPE CONNECTOR TERMINAL Power input Modb...

Page 5: ...ve 04 Read Input Registers X Collected data from the field by the slave 05 Force Single Coil X Digital output from the slave 06 Preset Single Registers X General purpose register within the slave 07 R...

Page 6: ...Y Y Y Y B16 Serial No 530 537 Y Y Y Y B16 Hardware version No 538 545 Y Y Y Y B16 Firmware version No Holding Register 4X 1 16 I Reserved for AO in 17 48 F Reserved for AO in engineering unit 145 160...

Page 7: ...each input type C for temperature Volts for voltage and for potentiometer The data are 32 bit floating values which requires two consecutive registers for one module 3 CHANNEL STATUS 30081 to 30096 I...

Page 8: ...E CRC 270 to 1000 C 0x13 J IC 210 to 1200 C 0x14 T CC 270 to 400 C 0x15 B RH 100 to 1820 C 0x16 R 50 to 1760 C 0x17 S 50 to 1760 C 0x18 C WRe 5 26 0 to 2320 C 0x19 N 270 to 1300 C 0x1A U 200 to 600 C...

Reviews: