background image

R1M-D1

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-5659  Rev.6  P. 7 / 8

 

INPUT REGISTERS DESCRIPTION

(1) ANALOG INPUT IN % (30001 to 30016; 30001 to 30008 for J3)

Indicates analog input values in percentage for each channel (1 – 16; 1 – 8 for J3).

INPUT TYPE & RANGE

A/D DATA (Decimal)

DC

±20 V

±20000

±5 V

±5000

±1 V

±10000

±0.8 V

±8000

±0.2 V

±20000

±50 mV

±5000

±10 mV

±10000

Thermocouple

Temperature 

5

 10

RTD

Temperature 

5

 10

Potentiometer

0 – 100 Ω
0 – 500 Ω
0 – 1 kΩ
0 – 10 kΩ

±2000

(2) ANALOG INPUT IN ENGINEERING UNIT (30017 to 30048; 30017 to 30032 for J3)

Indicates analog input values in engineering unit for each channel (1 – 16; 1 – 8 for J3).  The unit is specific to each input 
type: °C for temperature, Volts for voltage, and % for potentiometer.  The data are 32-bit floating values, which requires two 
consecutive registers for one module.

(3) CHANNEL STATUS (30081 to 30096)

Indicates the current status of analog inputs (1 – 16; 1 – 8 for J3).  The following list shows the names and descriptions of 
each bit.

BIT

NAME

DESCRIPTION

6

Input Overrange

Indicates the designated analog input is in overrange, defined as one or 
more of the following condition:

• ADC input value 0x0000 or 0xFFFF
• Burnout status for thermocouple, RTD and Potentiometer input
• Out of range defined in the temperature table (thermocouple and RTD)
• ADC error

0 : Normal
1 : Overrange

7

ADC Error

Indicates the status of ADC.
0 : Normal
1 : Error

12

Cold Junction Compensation SW

Indicates whether the cold junction compensation is enabled or disabled, 
for thermocouple input.
0 : Disable
1 : Enable

Others

Reserved

For system’s use

Summary of Contents for R1M-D1

Page 1: ...Okaya Electric Industries Model SUP E1H or equivalent for the power source connected to the unit and TDK Model ZCAT 3035 1330 or equivalent for the RS 232 C cable are recommended The equipment must be...

Page 2: ...fer to EXTERNAL DIMENSIONS TERMINAL CONNECTIONS Connect the module referring to the connection diagram EXTERNAL DIMENSIONS unit mm inch M3 SCREW TERMINALS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18...

Page 3: ...2 1 10 12 11 13 15 14 16 17 18 20 19 21 22 23 24 25 27 26 28 29 30 31 32 33 35 34 36 ch 1 ch 2 ch 3 ch 4 ch 5 ch 6 ch 7 ch 8 COM ch 9 ch 10 ch 11 ch 12 ch 13 ch 14 ch 15 ch 16 COM ch 17 ch 18 ch 19 ch...

Page 4: ...able wire size 0 75 to 1 25 mm2 AWG19 16 Recommended manufacturer Japan Solderless Terminal MFG Co Ltd Nichifu Co ltd 6 max 24 3 12 max 3 2 13 dia mm inch EURO TYPE CONNECTOR TERMINAL Power input Modb...

Page 5: ...ve 04 Read Input Registers X Collected data from the field by the slave 05 Force Single Coil X Digital output from the slave 06 Preset Single Registers X General purpose register within the slave 07 R...

Page 6: ...Y Y Y Y B16 Serial No 530 537 Y Y Y Y B16 Hardware version No 538 545 Y Y Y Y B16 Firmware version No Holding Register 4X 1 16 I Reserved for AO in 17 48 F Reserved for AO in engineering unit 145 160...

Page 7: ...each input type C for temperature Volts for voltage and for potentiometer The data are 32 bit floating values which requires two consecutive registers for one module 3 CHANNEL STATUS 30081 to 30096 I...

Page 8: ...E CRC 270 to 1000 C 0x13 J IC 210 to 1200 C 0x14 T CC 270 to 400 C 0x15 B RH 100 to 1820 C 0x16 R 50 to 1760 C 0x17 S 50 to 1760 C 0x18 C WRe 5 26 0 to 2320 C 0x19 N 270 to 1300 C 0x1A U 200 to 600 C...