EXPLANATIONS OF TERMS & FUNCTIONS

 SCALING FACTOR, INPUT PULSE SET COUNT & OUT-

PUT PULSE SET COUNT

The scaling factor, rate of number of output pulses divided 
by  number  of  input  pulses,  is  determined  by  two  param-
eters:  input pulse set count and output pulse set count.
The JPS3 output is designed to be proportional in number 
of pulses relative to the input.  For example, when the pulse 
rate is set to 0.0583, the JPS3, provided with 10000 input 
pulses (input 1 and 2 added), outputs 583 pulses.  However, 
the output is not supplied in a constant frequency.  The JPS3 
counts the number of input pulses during the sampling time 
(period) and stores it in the internal buffer counter, and pro-
vides the number of output pulses multiplied by the scaling 
factor  for  the  number  of  input  pulses,  by  the  end  of  next 
sampling cycle.  With the maximum output frequency limit, 
those pulses exceeding the limit are still in the buffer and 
output only in the following cycle.

 SAMPLING TIME

The sampling time is defined as a time period required by 
the JPS3 to count the input signals for one cycle.  With its 
factory  default  setting  (0.1  sec.),  the  output  is  refreshed 
every 100 milliseconds.
This setting is not usually be changed unless for a specific 
purpose.

 MAXIMUM OUTPUT FREQUENCY LIMIT

You  can  limit  the  maximum  output  frequency  from  the 
JPS3.
The JPS3 multiplies the number of input pulses by the scal-
ing factor.  However when the output pulses are supplied to 
a low-speed response counter, the number of output pulses 
(output frequency of the JPS3) may have to be limited with-
in a certain level.
Those surplus pulses remains in the buffer and are output 
in the following sampling cycles within the limit.

OUTPUT LOGIC

H

L

Voltage Pulse

or

RS-422

Line Driver Pulse

OUTPUT WAVEFORM

Open collector

or

Noncontact

AC/DC Switch

The pulse width in one-shot means the bold lined section of a pulse waveform.

*

As specified by the model number suffix code.

No pulse width conversion

One-shot, detecting input pulse rise

Non

Inverted

Voltage Pulse

2-wire Current Pulse

Open Collector or

Mechanical Contact

INPUT 1 & 2 WAVEFORM

H

H

L

H

H

L

L

H

L

OFF

ON

L

L

H

One-shot, detecting input pulse drop

H

L

No pulse width conversion

One-shot, detecting input pulse rise

Inverted

H

H

L

H

H

L

L

L

L

H

One-shot, detecting input pulse drop

OFF

ON

No pulse width conversion

One-shot, detecting input pulse rise

Non

Inverted

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

One-shot, detecting input pulse drop

No pulse width conversion

One-shot, detecting input pulse rise

Inverted

One-shot, detecting input pulse drop

*

*

*

*

Reviews: