JPS3
P. / 5
EM-575 Rev.
HARDWARE SETTING
• Noise Filter
‘High’ setting is used for the input frequency ≤10 Hz.
‘Low’ setting is used for the input frequency ≤500 Hz.
For mechanical contact input, ‘High’ setting is recommend-
ed to prevent typical chattering from counting.
DO NOT change the factory settings of SW1-1 through
SW1-6 and SW2-1 through SW2-6.
INPUT 1
INPUT 2
NOISE FILTER
SW1-7
SW1-8
SW2-7
SW2-8
High
ON
OFF
ON
OFF
Low
OFF
ON
OFF
ON
None
OFF
OFF
OFF
OFF
The switches in the table are set at the factory according to
the Ordering Information Sheet.
5
4
3
2
1
0
9 8 7 6
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Output Voltage Adj.
Unused
Unused
Unused
One-shot Pulse
Width Adj.
Input Type Selectors
Input Monitor LED (PL2)
Modular Jack
Output Monitor LED
Input Monitor LED (PL1)
The JPS3 is programmed and calibrated at the factory according to
the Ordering Information Sheet.
Please refer to the instruction manual for the model under “Software
Setting” when you need to modify certain specifications.
DO NOT change setting of unused switches and potentiometers.
SOFTWARE SETTING
Please refer to the Operation Manual for Model PU-2x (EM-9255), Section B: (B-1) Introduction, (B-2) General Operation
Description, (B-3) Operation Flowchart for general information.
[GROUP 01]
ITEM
MDF.
CODE
INPUT DATA
EXAMPLE (EXAMPLE)
DEFAULT
CONTENTS
0
S
0
MTSW : MON.MODE
MTSW : PRG.MODE
N/A
MAINTENANCE SWITCH
0 : Data indication only.
1 : All ‘P’ marked parameters are modifiable.
0
P
Alphanumeric TG : XXXXXXXXXX
N/A
Tag name entry (10 characters max.)
0
P
Numeric
CT1 : XXXXXX
0*
1
Total input 1 pulses (any count selectable)
0
P
Numeric
CT2 : XXXXXX
0*
1
Total input 2 pulses (any count selectable)
05
P
Numeric
IN : XXXXXX
Input pulse set count (1 to 1 000 000)
06
P
Numeric
OUT : XXXXXX
Output pulse set count (1 to 1 000 000)
07
P
Numeric (Hz)
FRQ : XXXX.XHz
0.0
Max. output frequency limit (0.5 to 100000.0 Hz)
08
P
Numeric (s)
SMP : X.XXs
0.0
Sampling time (0.01 to 100.00 s)
09
D
No input
SW : IN_V 1/20
SW : IN_V 1/10
SW : IN_V 1/5
SW : IN_V 1/2
SW : IN_V 1/1
SW : IN_V 5/1
SW : IN_V 10/1
SW : IN_OC, mA
SW : no use
SW : no use
N/A
Input specifications
SW = 0, Voltage input, Sensitivity scale = 1/20
SW = 1, Voltage input, Sensitivity scale = 1/10
SW = 2, Voltage input, Sensitivity scale = 1/5
SW = 3, Voltage input, Sensitivity scale = 1/2
SW = 4, Voltage input, Sensitivity scale = 1/1
SW = 5, Voltage input, Sensitivity scale = 5/1
SW = 6, Voltage input, Sensitivity scale = 10/1
SW = 7, Open collector, mechanical contact or two-wire current input
SW = 8, (not used)
SW = 9, (not used)
0
P
0
IN_EDGE : 0
IN_EDGE : 1
*
2
Count mode
Count at pulse rise
Count at pulse sink
*1. Reset to 0 when the power is lost.
*2. Factory set. DO NOT change this setting.
Modification Code
D : No modification (writing) possible. Used only for monitoring (reading).
S : Modifiable at any time.
P : Modifiable only when the MAINTENANCE SWITCH is in the ‘PRG’ mode.
ROM Version Indication
[GROUP 00] [ITEM 99]