background image

AS4R

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-1606  Rev.14  P. 5 / 5

 

CONNECTION DIAGRAM

U(+)

V(–)

POWER

7

8

10

11

9

2

3

1

L2 OUTPUT

L1 OUTPUT

N.C.

N.O.

COM

N.C.

N.O.

COM

 

SPDT RELAY

U(+)

V(–)

POWER

7

8

10

11

9

2

3

1

L4 OUTPUT

L1 OUTPUT

COM

L3 OUTPUT

L2 OUTPUT

COM

 

N.O. RELAY

 

N.C. RELAY

10

11

9

2

3

1

L4 OUTPUT

L1 OUTPUT

COM

L3 OUTPUT

L2 OUTPUT

COM

4

5

A

B

B

RTD

6

4

5

A

B

B

RTD

6

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 

7 – 8 with a multimeter.

3) Input:  Check voltage across the terminals 4 – 5 with a 

sensitive voltmeter.

   With 20°C or 68°F and input XΩ, the voltage across the 

terminals are given by:

X

× 1.18

(X + 1000)

   If the RTD or its extension wires are broken, the PV 

display indicates the upper range temperature limit 
and blinks (the lower range limit with downscale) due 
to burnout function.  Check leadwires in such a case.

4) Alarm operations:  Check the alarm operations referring 

to the figure below.

5) Output load:  Check that the output rating road is: 240 

V AC / 120 VA or 30 V DC / 30 W (240 V AC / 600 VA or 

30 V DC / 150 W for dual alarm, Output Code 5) at the 

maximum.  For maximum relay life with inductive load, 

external protection is recommended.

0

50

100

Input
(%)

LL

L

HH

H

L2 (1–2)

ON

L3 (1–3)

ON

L4 (9–11)

ON

OFF

OFF

L1 (9–10)

ON

OFF

OFF

Alarm Trip Operation                   

Terminal No. in parentheses

Example with quad N.O. contacts (LL, L, H, HH)

Trip Operation in Power Failure

• Output code 2: All relays turn off.
• Output code 3: All relays turn on.
• Output code 5: Terminals 1 – 3, 9 – 11 turn on.

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.

• H (HH) Setpoint

   Increase the input signal from a value lower than the set-

point and check that the relay trips at the H (or HH) set-
point within the setpoint accuracy described in the data 
sheet.

• L (LL) Setpoint

   Decrease the input signal from a value higher than the 

setpoint and check that the relay trips at the L (or LL) 
setpoint within the setpoint accuracy described in the 
data sheet.

When the setpoints are shifted, please contact M-System’s 
Sales Office or representatives.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

Reviews: