AS4R
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-1606 Rev.14 P. 3 / 5
FRONT VIEW & PROGRAMMING
■
L1
L2
L3
L4
ALARM
DATA
ITEM
DATA
ITEM
ITEM No. Display
DATA UP-DOWN Keys
ITEM No. UP-DOWN Keys
*
Monitor LEDs
DATA Display
*
L3 or L4 does not turn on for dual output type.
PROGRAMMING PROCEDURE
1) Press ITEM UP or DOWN key until ITEM display indicates “01”.
2) Press DATA UP or DOWN key and choose “1” or “2” on DATA
display.
1: Only alarm setpoints are modifiable.
2: All parameters are modifiable.
3) Press ITEM UP or DOWN key until ITEM display shows the
ITEM No. you need to change.
4) Press DATA UP or DOWN key and choose a DATA No. or value
you need on DATA display.
5) Repeat above 3 and 4. (Entered data is stored when you move to
a new ITEM.)
6) Press ITEM UP or DOWN key until ITEM display indicates “01”.
7) Press DATA UP or DOWN key and choose “0” on the display.
8) Press ITEM UP or DOWN key until ITEM display indicates “P”.
DATA display shows process input.
(You can now check data setting by choosing ITEM No.)
Note: DO NOT press UP and DOWN keys simultaneously.
ITEM
MDF.
CODE
DATA
CONTENTS
DEFAULT SETTING
P
N/A
-240 – 900.0*
1
Process input display in engineering unit
----
L1
L2
L3
L4
1, 2
1, 2
1, 2
1, 2
-240 – 900.0*
1
-240 – 900.0*
1
-240 – 900.0*
1
-240 – 900.0*
1
L1 alarm setpoint in engineering unit
L2 alarm setpoint in engineering unit
L3 alarm setpoint in engineering unit *
2
L4 alarm setpoint in engineering unit *
2
Quad: 20.0
Quad: 30.0
Quad: 70.0
Quad: 80.0
Dual: 20.0
Dual: 80.0
01
0, 1, 2
Modification code
0: Data indication only.
1: Only ITEM L1 – L4 are modifiable.
2: All parameters are modifiable.
1
02
N/A
00 – 99
Status indication (“0” is normally indicated.)
0: Normal 1: Memory error 10: Out of input range -15 – +115%
03
N/A
4
Input type 4: RTD
04
2
0 – 99
Power ON-delay time (seconds)
5
05
2
0 – 99
Alarm ON-delay time (seconds)
0
06
2
0, 1, 2, 3, 4
Moving average (sampling cycle: 100 msec.)
0: No, 1: 4 samples, 2: 8 samples, 3: 16 samples, 4: 32 samples
0
07
08
09
10
2
2
2
2
0, 1
0, 1
0, 1
0, 1
L1 trip operation
L2 trip operation
L3 trip operation
L4 trip operation
(0: Lo, 1: Hi)
(0: Lo, 1: Hi)
(0: Lo, 1: Hi) *
2
(0: Lo, 1: Hi) *
2
Quad: 0
Quad: 0
Quad: 1
Quad: 1
Dual: 0
Dual: 1
11
2
-1, 0, 1 – 60
Power-saving mode
-1: Continuous display upon startup
0: Continuous display after the last access
1 – 60: Time before display turned off (minutes)
10
12
13
14
15
2
2
2
2
0, 1
0, 1
0, 1
0, 1
L1 coil at alarm (0: Energized, 1: De-energized)
L2 coil at alarm (0: Energized, 1: De-energized)
L3 coil at alarm (0: Energized, 1: De-energized)*
2
L4 coil at alarm (0: Energized, 1: De-energized)*
2
0
0
0
0
16
N/A
----
Version No. indication
----
17
18
19
20
2
2
2
2
0.0 – 900.0
0.0 – 900.0
0.0 – 900.0
0.0 – 900.0
L1 hysteresis (deadband) in engineering unit
L2 hysteresis (deadband) in engineering unit
L3 hysteresis (deadband) in engineering unit*
2
L4 hysteresis (deadband) in engineering unit*
2
1.0
1.0
1.0
1.0
21
2
0, 1
Burnout (0: Downscale, 1: Upscale)
1
22
2
-240 – 900.0*
1
Upper range temperature limit
Display blinking with higher temperature
500.0
PV blinking at upscale burnout
23
2
-240 – 900.0*
1
Lower range temperature limit
Display blinking with lower temperature
-100.0
PV blinking at downscale burnout
24
2
0, 1, 2
Temperature unit (0: °C, 1: °F, 2: K)
0