AS4R
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-1606 Rev.14 P. 4 / 5
ITEM
MDF.
CODE
DATA
CONTENTS
DEFAULT SETTING
25
2
0 – 7
RTD type
0: JPt 100 (JIS ’89), 1: Pt 100 (JIS ’89),
2: Pt 100 (JIS ’97, IEC), 3: Pt 50 Ω (JIS ’81)
4: Ni 508.4 Ω, 5: Pt 1000, 6: Ni 100, 7: Cu 10 @25°C
2: Pt 100 (JIS ’97, IEC)
*1. It operates simultaneously with the display unit of ITEM 24. Refer to the table 1 for available setting range.
*2. Quad alarm trip type only
Table 1: USABLE RANGE
RTD
USABLE RANGE
°C
°F
K
JPt 100 (JIS ’89)
-235 – +560.0
-391 – +1040
38.2 – 833.2
Pt 100 (JIS ’89)
-240 – +900.0
-400 – +1652
33.2 – 1173
Pt 100 (JIS ’97, IEC)
-240 – +900.0
-400 – +1652
33.2 – 1173
Pt 50 Ω (JIS ’81)
-235 – +700.0
-391 – +1292
38.2 – 973.2
Ni 508.4 Ω
-100.0 – +330.0
-148.0 – +572.0
173.2 – 603.2
Pt 1000
-240 – +900.0
-400 – +1652
33.2 – 1173
Ni 100
-100.0 – +250.0
-148.0 – +482.0
173.2 – 523.2
Cu 10 @ 25°C
-210 – +310.0
-346 – +590.0
63.2 – 583.2
* Minimum step
-199.9 to 999.9: 0.1
Not greater than -200, not lower than 1000: 1
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the top of the unit.
■
EXTERNAL DIMENSIONS unit: mm (inch)
• When mounting, no extra space is needed between units.
5
6
7
8
2
1
11
10
80 (3.1
5)
40 (1.57)
50 (1.97)
7.8 (.31)
2
–
4.5 (.18) dia.
MTG HOLE
25 (.98) deep
11
–
M3.5
SCREW
3
9
4
For wiring connection, refer to “TERMINAL CONNECTIONS” and wire correctly.
Fire, electric shock and failure cause if wire are incorrectly connected.
80 (3.1
5)
50 (1.97)
103 (4.06)
132 (5.20)
20 (.79)
[3.3 (.13)]
CLAMP
(top & bottom)
DIN RAIL
35mm wide