background image

71VR1

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201   Fax: +81(6)6659-8510   E-mail: [email protected]

EM-7403-A Rev.7

  P. 4 / 8

NSTALLATION

 CAUTION

• Degree of protection, IP65 is applicable to the front panel 

of the unit with single mounting according to the specified 
panel cutout. 

• Install the unit to vertical panel so that its function but

-

tons are at the bottom side.  Installing by other direction 
will cause degradation of life span or performance due to 
rise of the internal temperature.

• Ensure that there is sufficient space for ventilation inside 

a panel.  Do not install above the devices that generate 
high heat such as heaters, transformers or resistors.  Ob-
serve at the minimum of 30 mm (1.2”) in all directions for 
maintenance purpose.

 HOW TO MOUNT THE UNIT ON A PANEL

1)  Remove the mounting brackets.
2) Remove the terminal cover and insert it into the panel 

cutout prior to insertion of the unit.

3) Insert the unit into the panel cutout.  The watertight 

packing must be in place to hold the unit.  Do not remove 
it.

4) 

Hang the hooks of the mounting brackets at the square 

holes on the upper and bottom side of the unit.  Tighten 
screws of the brackets until the unit is fixed to the panel.

Panel

Mounting Bracket

Watertight Sealing

92

92

+0.

8

  

0

+0.8
  0

 PANEL CUTOUT unit: mm

Usable panel thickness: 0.5 – 10

 HOW TO REMOVE THE TERMINAL COVER

Insert the minus tip of a screwdriver into each hole at the 
four corners of the cover and pull it to the direction as indi-
cated below to separate the terminal cover.

 HOW TO REMOVE THE TERMINAL BLOCK

• The terminal block is separable in two pieces.  Loosen two 

screws on top and bottom of the terminal block to sepa-
rate.

• Be sure to turn off the power supply, input/output signal, 

communication signal and power supply to the output re-
lays before separating the terminal block.

• Each terminal block has ID keys so that it can be inserted 

to applicable terminal socket only.

Terminal Block Screw

Terminal Block ID Key

Terminal
Block

Separable

Terminal Block ID Key

Summary of Contents for 71VR1

Page 1: ...ic insulation is between analog input each other contact input contact output each other and network interface Prior to instal lation check that the insulation class of this unit satisfies the system...

Page 2: ...ult a doctor The following phenomena are LCD characteristics and NOT a product defect LCD screen may show uneven brightness depending upon displayed images The LCD screen pixels may contain minute bla...

Page 3: ...ement display CONTROL MENU and SETTING MENU cancel the operation 5 F2 F5 button Change display pages operation of menu or cursor change setting values 6 F6 button Mark to measured values ENTER execute...

Page 4: ...tion of the unit 3 Insert the unit into the panel cutout The watertight packing must be in place to hold the unit Do not remove it 4 Hang the hooks of the mounting brackets at the square holes on the...

Page 5: ...tion 2 3 4 5 6 7 8 1 FE 1 2 SHLD T4 T1 T2 T3 11 A1 B1 C1 A2 B2 C2 A3 B3 C3 13 12 14 16 15 17 19 18 Universal Input A B B RTD A B A B C A B C A B B C A B C A C T C REM2 CJC SENSOR C COM 21 23 22 24 26...

Page 6: ...urns to green How to remove a memory card 1 When the unit is recording press STOP RECORDING button in the CONTROL MENU to stop recording 2 Press the REMOVE MEMORY CARD button in the CONTROL MENU 3 Pus...

Page 7: ...or INPUT CHANNEL 3 Press F2 or F3 button to select FIELD CHANNEL then press EDIT F6 button to enable editing 4 Press F2 or F3 button to select Ai1 then press ENTER F6 button to set the field channel t...

Page 8: ...recording to memory card 3 Press F1 button to confirm REC in the sub display of TREND display screen or DIGITAL display screen turns to red STOP RECORDING 1 Press F1 button several times to display C...

Reviews: