background image

71VR1

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201   Fax: +81(6)6659-8510   E-mail: [email protected]

EM-7403-A Rev.7

  P. 2 / 8

• Do  not  store  or  use  the  unit  in  environments  subject  to 

chemical evaporation (such as that of organic solvents), or 
where there are chemicals and/or acids present in the air.

• Do not use paint thinner or organic solvents to clean the 

unit.

• 

Observe the environmental conditions when using the unit.

• Wait at least for 15 seconds before turning on the power 

supply after it has been turned off.

 ENVIRONMENT

• Indoor use
• The unit is designed to be mounted on a vertical panel.  It 

is not suitable for a slanted or a horizontal panel surface.

• Environmental temperature must be within -5 to +55°C 

(23 to 131°F) with relative humidity within 30 to 90% RH 

in order to ensure adequate life span and operation.

 GROUNDING

• Be sure to determine in advance the most stable ground

-

ing point in the environment and earth the unit’s FE ter-
minal and that of connected devices to it in order to pro-
tect the devices from dielectric breakdown.

• Grounding is also effective to eliminate noise that could 

cause errors in the unit’s operation.

 MEMORY CARD

• Do not turn off the power supply to the unit or reset it dur

-

ing recording.  The memory card may be destroyed.

• Observe the described procedure when you need to replace 

the memory card during recording.

• Confirm the sides and the connector position of the mem

-

ory card when inserting one to the card slot.

• Do not touch the metal terminal with your hands or me

-

tallic tools.

• Memory cards have a life span.  Back up your important 

data.

 LCD PANEL

• The LCD panel’s liquid contains an irritant.  If the panel 

is damaged and the liquid contacts your skin, rinse imme-
diately the contact area with running water for at least 15 
minutes.  If the liquid gets in your eyes, rinse immediately 
your eyes with running water for at least 15 minutes and 
consult a doctor.

• The  following  phenomena  are  LCD  characteristics,  and 

NOT a product defect:

  - LCD screen may show uneven brightness depending 

upon displayed images.

  - The LCD screen pixels may contain minute black-and-

white-colored spots.

 - 

The color displayed on the LCD screen may appear differ-

ent when seen from outside the specified viewing angle. 

  - When the same image is displayed on the screen for a 

long time period, an afterimage may appear when the im-
age is changed.  If this happens, turn off the unit and wait 
15 seconds before restarting it.

• To prevent an afterimage plan to change the screen image 

periodically so that the same image does not remain for 
the long time period.

 MINIMIZING NOISE INTERFERENCE TO ANALOG SIGNAL CABLES

• Noise  entering  through  the  analog  signal  cables  may 

cause irregular measurement values, degradation of over-
all accuracy, and malfunction of the product.  We recom-
mend that you would conduct wiring to the unit with the 
following points of caution.

• Do  not  install  cables  (power  supply,  input  and  output) 

close to noise sources (high frequency line, etc.).

• Do not bind the analog I/O cables together with those in 

which noises are present.  Do not install them in the same 
duct.

 DO NOT APPLY OVERRANGE INPUT

• Do  not  apply  voltages  exceeding  ±15V  to  terminals  V 

– COM and AB – C to prevent damage.  Do not apply cur-
rents exceeding ±30mA to terminals I – COM to prevent 
damage.

 INTERNAL CLOCK

• The internal clock data is stored in memory powered by a 

backup battery while the unit is without external power 
supply.

• The data will be reset to its default status when the bat

-

tery is used up while the unit is left without power supply 
for a long time period.  The clock adjustment will be neces-
sary once the power is restored.

• Once the power is restored, the unit starts recharging the 

battery.  It will be full in approximately in 36 to 48 hours.

• Battery backup: approx. one month

 AND ....

• We recommend use of an UPS to supply power backups.
• The unit is designed to function as soon as power is sup

-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

Summary of Contents for 71VR1

Page 1: ...ic insulation is between analog input each other contact input contact output each other and network interface Prior to instal lation check that the insulation class of this unit satisfies the system...

Page 2: ...ult a doctor The following phenomena are LCD characteristics and NOT a product defect LCD screen may show uneven brightness depending upon displayed images The LCD screen pixels may contain minute bla...

Page 3: ...ement display CONTROL MENU and SETTING MENU cancel the operation 5 F2 F5 button Change display pages operation of menu or cursor change setting values 6 F6 button Mark to measured values ENTER execute...

Page 4: ...tion of the unit 3 Insert the unit into the panel cutout The watertight packing must be in place to hold the unit Do not remove it 4 Hang the hooks of the mounting brackets at the square holes on the...

Page 5: ...tion 2 3 4 5 6 7 8 1 FE 1 2 SHLD T4 T1 T2 T3 11 A1 B1 C1 A2 B2 C2 A3 B3 C3 13 12 14 16 15 17 19 18 Universal Input A B B RTD A B A B C A B C A B B C A B C A C T C REM2 CJC SENSOR C COM 21 23 22 24 26...

Page 6: ...urns to green How to remove a memory card 1 When the unit is recording press STOP RECORDING button in the CONTROL MENU to stop recording 2 Press the REMOVE MEMORY CARD button in the CONTROL MENU 3 Pus...

Page 7: ...or INPUT CHANNEL 3 Press F2 or F3 button to select FIELD CHANNEL then press EDIT F6 button to enable editing 4 Press F2 or F3 button to select Ai1 then press ENTER F6 button to set the field channel t...

Page 8: ...recording to memory card 3 Press F1 button to confirm REC in the sub display of TREND display screen or DIGITAL display screen turns to red STOP RECORDING 1 Press F1 button several times to display C...

Reviews: