INSTALLATION

 

MOUNTING THE ENCLOSURE ON A PIPE

 

MOUNTING THE ENCLOSURE ON A WALL

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.

6

5

1

2

LOAD

OUTPUT

24V DC

4 − 20mA DC

+

+

INPUT

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.6 N·m

CHECKING

Open the unit’s outdoor enclosure cover when you conduct 
checking of the transmitter.  Be sure to close the cover after 
the checking is complete.

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

3) Output:  Check that the load is within the permissible 

limit including wiring resistance.  

Load Resistance (Ω) = 

Supply Voltage (V) – 13 (V)

0.02 (A)

(including leadwire resistance)