INSTALLATION
■
MOUNTING THE ENCLOSURE ON A PIPE
■
MOUNTING THE ENCLOSURE ON A WALL
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
6
5
1
2
LOAD
OUTPUT
24V DC
4 − 20mA DC
+
−
+
−
INPUT
WIRING INSTRUCTIONS
■
SCREW TERMINAL
Torque: 0.6 N·m
CHECKING
Open the unit’s outdoor enclosure cover when you conduct
checking of the transmitter. Be sure to close the cover after
the checking is complete.
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Input: Check that the input signal is within 0 – 100% of
the full-scale.
3) Output: Check that the load is within the permissible
limit including wiring resistance.
Load Resistance (Ω) =
Supply Voltage (V) – 13 (V)
0.02 (A)
(including leadwire resistance)