53U
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6485-B Rev.21 P. 51 / 52
■
SETTING ALARM OUTPUT
Measurand: Current
Low setpoint: 50 A
High setpoint: 120 A
Hysteresis (deadband): 1%
Alarm ON delay time: 1 second
Discrete output: DO1
Change Setting
(SETTINGS)
Discrete I/O Setting
(DIO)
Discrete output 1 function
(DO1-FUNC)
ALARM : Alarm output
Discrete output 1 mode
(DO1-TYPE)
N-O : Normally open contact
Alarm Output Setting
(ALARM)
Measurands
I1-3
High setpoint
(HIGH)
120A
50A
Low setpoint
(LOW)
Hysteresis (deadband)
(HYSTERES)
1.0
1
Alarm ON delay time
(ON DELAY)
DOUT1
Alarm output
(OUTPUT)
■
SETTING ENERGY COUNT OUTPUT
Measurand: Active energy
Pulse weight: 1 kWh/count
ON pulse width: 500 msec.
Discrete output: DO2
Change Setting
(SETTINGS)
Discrete I/O Setting
(DIO)
Discrete output 2 function
(DO2-FUNC)
ENERGY : Energy count pulse
Discrete output 2 mode
(DO2-TYPE)
N-O : Normally open contact
Energy Setting
(ENERGY)
Pulse output 2
(COUNT2)
EP : Active energy
Pulse weight 2
(WEIGHT2)
1.0
Pulse width 2
(DURATION2)
500