53U
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6485-B Rev.21 P. 15 / 52
ADDR.
WORD
PARAMETER
6116
1
Discrete input contact type
0 : Normally open contact (*)
1 : Normally closed contact
6117
1
Discrete output 2 function
0 : Undefined (*)
1 : Energy count
2 : Alarm
6118
1
Discrete output 2 contact type
0 : Normally open contact (*)
1 : Normally closed contact
The contact opens at the power OFF regardless of this setting.
6121
1
Discrete output 3 function
0 : Undefined (*)
1 : Energy count
2 : Alarm
6122
1
Discrete output 3 contact type
0 : Normally open contact (*)
1 : Normally closed contact
The contact opens at the power OFF regardless of this setting.
6125
1
Discrete output 4 function
0 : Undefined (*)
1 : Energy count
2 : Alarm
6126
1
Discrete output 4 contact type
0 : Normally open contact (*)
1 : Normally closed contact
The contact opens at the power OFF regardless of this setting.
(*) Factory setting
■
ENERGY SETTING
DO
ADDR.
WORD
PARAMETER
UNIT
6241
1
Energy count 1 assigned to the discrete output 1
Refer to the table in the following page.
—
6242
2
Pulse weight for Energy count 1
0 : No pulse output (disabled)
1 to 100 000 : Specified value × 0.1 (kWh / kvarh / kVA)
Factory setting : 10
kWh/10
kvarh/10
kVA/10
6244
1
Pulse duration (width) for Energy count 1
1 to 20 : Specified value × 100 msec.
Factory setting : 1
sec/10
6245
1
Tariff setting for Energy count 1
0 : Disable (*)
1 : Enable
—
6246
1
Energy count 2 assigned to the discrete output 2
Refer to the table in the following page.
—
6247
2
Pulse weight for Energy count 2
0 : No pulse output (disabled)
1 to 100 000 : Specified value × 0.1 (kWh / kvarh / kVA)
Factory setting : 10
kWh/10
kvarh/10
kVA/10
6249
1
Pulse duration (width) for Energy count 2
1 to 20 : Specified value × 100 msec.
Factory setting : 1
sec/10
6250
1
Energy count 3 assigned to the discrete output 3
Refer to the table in the following page.
—
6251
2
Pulse weight for Energy count 3
0 : No pulse output (disabled)
1 to 100 000 : Specified value × 0.1 (kWh / kvarh / kVA)
Factory setting : 10
kWh/10
kvarh/10
kVA/10
6253
1
Pulse duration (width) for Energy count 3
1 to 20 : Specified value × 100 msec.
Factory setting : 1
sec/10