53U
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6485-B Rev.21 P. 32 / 52
ADDR. WORD
ID
PARAMETER
UNIT
961
963
965
2
2
2
I1 MIN
I2 MIN
I3 MIN
Current MIN, Line 1
Current MIN, Line 2
Current MIN, Line 3
mA
mA
mA
967
2
IN MIN
Neutral current MIN
mA
969
971
973
2
2
2
U12 MIN
U23 MIN
U31 MIN
Delta voltage MIN, 1 – 2
Delta voltage MIN, 2 – 3
Delta voltage MIN, 3 – 1
V/100
V/100
V/100
975
977
979
2
2
2
U1N MIN
U2N MIN
U3N MIN
Phase voltage MIN, Phase 1
Phase voltage MIN, Phase 2
Phase voltage MIN, Phase 3
V/100
V/100
V/100
981
983
985
2
2
2
P1 MIN
P2 MIN
P3 MIN
Active power MIN, Phase 1
Active power MIN, Phase 2
Active power MIN, Phase 3
W
W
W
987
989
991
2
2
2
Q1 MIN
Q2 MIN
Q3 MIN
Reactive power MIN, Phase 1
Reactive power MIN, Phase 2
Reactive power MIN, Phase 3
var
var
var
993
995
997
2
2
2
S1 MIN
S2 MIN
S3 MIN
Apparent power MIN, Phase 1
Apparent power MIN, Phase 2
Apparent power MIN, Phase 3
VA
VA
VA
999
1001
1003
2
2
2
PF1 MIN
PF2 MIN
PF3 MIN
Power factor MIN, Phase 1
Power factor MIN, Phase 2
Power factor MIN, Phase 3
1/10 000
1/10 000
1/10 000
■
TOTAL HARMONIC DISTORTION (THD)
ADDR. WORD
ID
PARAMETER
UNIT
1281
2
THD I1
Current total harmonic distortion, Line 1
%/10
1283
2
THD I2
Current total harmonic distortion, Line 2
%/10
1285
2
THD I3
Current total harmonic distortion, Line 3
%/10
1287
2
THD IN
Neutral current total harmonic distortion
%/10
1289
2
THD U12
Delta voltage total harmonic distortion, 1 – 2
%/10
1291
2
THD U23
Delta voltage total harmonic distortion, 2 – 3
%/10
1293
2
THD U31
Delta voltage total harmonic distortion, 3 – 1
%/10
1295
2
THD U1N
Phase voltage total harmonic distortion, Phase 1
%/10
1297
2
THD U2N
Phase voltage total harmonic distortion, Phase 2
%/10
1299
2
THD U3N
Phase voltage total harmonic distortion, Phase 3
%/10