EM-9442  Rev.8  P. 9 / 9

 

ZERO ADJUSTMENT

1) Apply 0% input signal.
2) Hold down [M] for 3 seconds* and push [M] to choose [Z].
3) Press [SET], and the bargraph shows 0%.

 

SPAN ADJUSTMENT

1) Apply 100% input signal.
2) Hold down [M] for 3 seconds* and push [M] to choose [S].
3) Press [SET], and the bargraph shows 100%.

 

ALARM SETPOINT ADJUSTMENTS

• 48NAVA-2:  H 

[L setpoint] to 100%

     

 

 

0% to [H setpoint]

     

 

 

No alarm trip is selectable

• 48NAVA-4:  HH 

[H setpoint] to 100%

     

 

 

[L setpoint] to [HH setpoint]

     

 

 

[LL setpoint] to [H setpoint]

     

 

 

LL 

0% to [L setpoint]

     

 

 

No alarm trip is selectable

• How to Set LL (or L, H, HH) Setpoints

1) Hold down [M] for 3 seconds* and push [M] to choose 

[LL].

2) Press [UP] or [DOWN] buttons until the indicator comes 

to the desired position, and press [SET].  

  (Same procedure for L, H, HH setpoints)

• How to Cancel HH and H Alarms

1) Press [UP] or [DOWN] buttons until the indicator comes 

to the upper limit, and press [SET].  

  HH indicator must be set before H as the H setpoint can-

not go above the HH setpoint.

• How to Cancel LL and L Alarms

1) Press [UP] or [DOWN] buttons until the indicator comes 

to the lower limit, and press [SET].  

  LL indicator must be set before L as the L setpoint can-

not go below the LL setpoint.

 

DC OUTPUT FINE ZERO ADJUSTMENT (0%)

1) Apply 0% input signal.
2) Hold down [M] for 3 seconds* and push [M] to choose [Z].
3) Press [UP] and [DOWN] buttons at once for two times 

until the Z indicator changes from blinking to solid to 

blinking in double speed.

4) Press [UP] or [DOWN] buttons to show a desired value at 

the receiving instrument, and press [SET].  

 

DC OUTPUT FINE SPAN ADJUSTMENT (100%)

1) Apply 100% input signal.
2) Hold down [M] for 3 seconds* and push [M] to choose [S].
3) Press [UP] and [DOWN] buttons at once for two times 

until the S indicator changes from blinking to solid to 

blinking in double speed.

4) Press [UP] or [DOWN] buttons to show a desired value at 

the receiving instrument, and press [SET].

 

SIMULATED OUTPUT

1) Hold down [DOWN] for longer than 5 seconds to enter 

the simulation mode until the Z and S indicators start 

blinking.

2) Press [UP] or [DOWN] buttons to simulate a desired DC 

output.  Programmable from 0 to 100%.

3) Hold down [SET] for longer than 5 seconds to get out of 

the simulation mode.

*  The [M] button remain activated for 1 minute after it has 

been used to choose a indicator LED (programming mode).  
During this period, pressing the [M] button briefly is enough 
to choose another indicator.  After 1 minute, it turns to deac-
tivated state.

CALIBRATION PROCEDURE

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.
For matching the indication to a receiving instrument or in 
case of regular calibration, adjust the output as explained 
in the following.

 

HOW TO CALIBRATE THE OUTPUT INDICATION

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.

1) ZERO:  Apply 0% input and adjust bargraph and DC out-

put to 0% following the procedure explained in “ADJUST-

MENT PROCEDURE.”

2) SPAN:  Apply 100% input and adjust bargraph and DC 

output and DC output to 100% following the same proce-

dure.

3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-

dure 1) – 3).

MAINTENANCE

Regular checking procedure is explained below:

 

CHECKING

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the bargraph  
and DC output for the respective input signal remains with-
in accuracy described in the data sheet.  When the bargraph 
and DC output are out of tolerance, recalibrate the unit ac-
cording to the “CALIBRATION PROCEDURE” explained 
earlier.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protectors for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

Summary of Contents for 48NAVA

Page 1: ...ironments such as panel con figurations connected devices connected wires may affect the protection level of this unit when it is integrated in a panel system The user may have to review the CE or UKC...

Page 2: ...NENT IDENTIFICATION 50 40 30 20 10 0 10 20 30 40 50 m3 h 100 SET H S Z L 90 80 70 60 50 40 30 20 10 0 M Brackets Body A Scale Plate Pull up the part A when replacing the scale plate INSTALLATION PANEL...

Page 3: ...mm Slide the top and bottom parts of the bezel into the back of the front cover as shown below Bezel When multiple units are to be clustered side by side insert one bezel between two units as shown be...

Page 4: ...13 14 15 16 16 M3 SCREW TERMINALS Rounded corners for the option D 2 M3 SCREWS 144 5 67 137 5 5 41 4 1 16 36 1 42 OPTION D BEZEL 3 1 Space required when replacing the scale plate 2 Used for the exist...

Page 5: ...UTPUT L OUTPUT ALARM OUTPUT CODE 2 2 points 5 6 INPUT 5 6 ALARM OUTPUT CODE 4 4 points 12 13 14 15 16 U V LLa 11 La LLb Lc LLc 8 9 10 HHa 7 Hc HHc HHb Ha HH OUTPUT H OUTPUT LL OUTPUT L OUTPUT POWER DC...

Page 6: ...r amber Zero Adj amber L Setpoint Adj Trip Indicator green UP Button Mode Selector DOWN Button H Setpoint L Setpoint PV Indicator M 50 40 30 20 10 0 10 20 30 40 50 m3 h 100 SET L Z S 90 80 70 60 50 40...

Page 7: ...inking Mode Selector 1 ZERO ADJUSTMENT Apply 0 input signal before adjustment Z SET Z M Zero Adjustment Complete LED OFF LED Blinking Mode Selector 1 S SET S M Span Adjustment Complete SPAN ADJUSTMENT...

Page 8: ...tput between 0 and 100 The bargraph shows the simulated output 4 Keep pressing SET button at least for 5 seconds to exit the simulated output mode Note Each setting sequence is complete only when SET...

Page 9: ...double speed 4 Press UP or DOWN buttons to show a desired value at the receiving instrument and press SET SIMULATED OUTPUT 1 Hold down DOWN for longer than 5 seconds to enter the simulation mode until...

Reviews: