background image

47LR

P. 4 / 4

EM-9503-B Rev.

M-SYSTEM WARRANTY

M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such 
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System’s sole liability, and purchaser’s exclusive 
remedies, under this warranty are, at M-System’s option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this 
warranty.  To submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original 
sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED 
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.  M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR 
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]

ERROR MESSAGES

MAIN DISPLAY

Input error, Out of the measuring range
Input wire breakdown (burnout)
Non-volatile memory error (reading)
Non-volatile memory error (writing)

*

1.  All parameter settings are reset to the factory default values.  If the unit does not recover its function after the initialization, repairing

 

in the factory may be required.

Increase/decrease the input signal until it is back within the measuring range.
Check the input wires.
While the error message is on the display, press Up button for 3 seconds or 

more to initialize the unit to its factory default status.

*

1

 

Repair is needed if the display does not recover after the power is reset.

ERROR MESSAGE

WHAT TO DO

Internal data error

CHARACTER SET

0 1 2

4

3

5 6 7

9

8

– A B

D

C

E F G

I

H

J K L

N

M

O P Q

S

R

T U V W X

Z

Y

 LOOP TEST OUTPUT MODE

Shift

Loop Test Output

Measuring Mode

-1999...9999

Set value

Setting Parameters

Hold down Alarm/    + Init/    + Shift

button for 

5 seconds

Hold down Alarm/    or Init/    button

for 

1 second

Loop Test Output Mode

*

1. Hold down Alarm/    or Init/    button for 

1 second to return to the measuring mode while setting parameters.

*

1

PARAMETER

Loopt test output: Pressing [Shift] button switches the signal to increase (          ON) or decrease (          ON), and then pressing [Up] 

 

button controls it toward the desired output value.

 

Alarm trip functions according to the temperature values during the loop test.

*

1.  Temperature value can be specified within the usable range for the respective sensor types.

 

The specified decimal point position is applied to the loop test output value.

INDICATORS

/

FUNCTION

DEFAULT

VALUE

DISPLAY

Adj Fnc

Min

Max

...

Loop test output

Temperature value for the loop test output

(display blinking)

Ini Alm D/P

N/A

Max

Min

*

1

LIGHTNING SURGE PROTECTION

M-System  offers  a  series  of  lightning  surge  protectors  for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

Summary of Contents for 47LR

Page 1: ...icate it POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 100 240V AC rating 85 264V 50 60 Hz approx 6 5VA...

Page 2: ...alarm setting mode or to shift through setting items in each setting mode 6 Init button Used to move on to the initial setting mode or to shift through setting items in each setting mode 7 Shift butt...

Page 3: ...must be in place to hold the meter Do not remove it 1 Insert the unit into the panel cutout 2 Push the mounting brackets into the grooves on both sides of the rear module until they hit the panel s r...

Page 4: ...b NC Ha NO 17 15 16 20 18 19 Lc LLc LLa La Hc HHc Ha HHa LL OUTPUT L OUTPUT H OUTPUT L OUTPUT H OUTPUT HH OUTPUT 9 10 POWER U V ALARM SUFFIX CODE 2 SPDT contact 2 points 9 10 POWER U V ALARM SUFFIX CO...

Page 5: ...Hold down Max Min Alarm buttons at once for a preset time duration 1 Hold down Alarm Init buttons at once for 3 seconds POWER ON 1 INITIAL SETTING FLOWCHART Initial Setting Complete Measuring Started...

Page 6: ...t button shifts one to the previous Changing parameters Pressing Shift button while one of the parameter settings is indicated on the display shifts the panel meter into the setting standby mode The d...

Page 7: ...eters 1999 9999 UP DOWN 1 Hold down Init button for 3 seconds Hold down Alarm or Init button for 1 second Shift Shift Alarm Alarm Alarm Alarm Alarm Alarm Alarm Shift Shift Alarm Alarm Initial Setting...

Page 8: ...decimal fraction is specified Temperature values must be re set if the decimal point position is shifted Temperature input offset setting 4 Pt 100 JIS 97 IEC 5 Pt 50 JIS 81 1 decimal place No decimal...

Page 9: ...Init Alarm Alarm Init Alarm Alarm Setting Mode Alarm Shift L Setpoint L Deadband L ON Delay Time 1999 9999 0000 9999 00 99 Shift Shift Alarm Init Alarm Alarm Init Alarm Alarm Init Alarm Init L Coil a...

Page 10: ...ix code 2 is specified A B B B B B B Init HH ON Delay Time 00 99 Shift Alarm Init Alarm Alarm Init Alarm Init HH Coil at Alarm RYEN RYDN Shift Init Init Init Alarm Init Alarm Shift HH Setpoint 1999 99...

Page 11: ...m H Coil energized at alarm H Fnc H Coil de energized at alarm D P H Fnc H P Fnc HH setpoint HH deadband hysteresis HH ON delay time HH ON delay time seconds HH Deadband hysteresis value HH Setpoint v...

Page 12: ...ghtness level 4 Brightness level 5 bright Brightness level 3 Brightness level 2 No moving averaging INDICATORS FUNCTION DEFAULT VALUE DISPLAY Fnc D P Fnc D P Fnc D P Fnc Transition time to Lockout Set...

Page 13: ...for a preset time 1 1 Preset time can be specified with Transition Time to Lockout Setting Mode in Advanced Setting Mode A Init Init Init Init Set value Setting Parameters A Alarm setting lockout Lock...

Page 14: ...If the unit does not recover its function after the initialization repairing in the factory may be required Increase decrease the input signal until it is back within the measuring range Check the inp...