5545027-LTG-A-0618
40
Johnson Controls Unitary Products
PERFORMANCE DATA - 2 TON
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °
F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
CONDENSER-ONLY DATA (OUTDOOR UNIT)
MODEL
SATURATED SUCTION
@ COMPRESSOR
Outdoor Ambient Temperature
55 °F
65 °F
75 °F
85 °F
95 °F
105 °F
115 °F
125 °F
T (°F)
P (PSIG)
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
YFK24B21S
(Stage 2)
35
107
21.2
1.17
20.3
1.29
19.2
1.42
18.1
1.56
17.0
1.72
15.8
1.91
14.6
2.12
13.3
2.37
40
118
23.8
1.09
22.8
1.22
21.7
1.34
20.6
1.48
19.4
1.63
18.2
1.81
16.8
2.01
15.4
2.23
45
130
25.6
1.15
24.5
1.28
23.3
1.41
22.0
1.55
20.7
1.70
19.4
1.90
17.9
2.11
16.3
2.35
50
142
28.0
1.14
26.8
1.27
25.6
1.40
24.3
1.54
22.8
1.70
21.3
1.89
19.7
2.10
18.1
2.34
55
156
30.7
1.13
29.4
1.26
28.0
1.39
26.5
1.53
25.1
1.69
23.4
1.88
21.7
2.09
20.0
2.33
YFK24B21S
(Stage 1)
35
107
14.7
0.84
13.9
0.95
13.0
1.06
12.2
1.20
11.3
1.35
10.3
1.53
9.2
1.71
8.1
1.92
40
118
16.3
0.82
15.3
0.93
14.5
1.05
13.6
1.19
12.6
1.33
11.6
1.50
10.5
1.69
9.2
1.90
45
130
18.1
0.80
17.0
0.91
16.0
1.03
15.0
1.16
14.1
1.31
13.0
1.48
11.8
1.67
10.5
1.87
50
142
20.1
0.78
18.8
0.88
17.7
1.00
16.6
1.14
15.5
1.29
14.5
1.45
13.3
1.65
11.9
1.84
55
156
22.1
0.75
20.7
0.86
19.5
0.98
18.4
1.11
17.2
1.26
16.0
1.44
14.7
1.62
13.4
1.81
Notes:
1. For Outdoor Unit (Condenser) performance only. Data does not include the effects of air handler power or heat.
2. Performance based on 15°
F subcooling and 15°
F superheat at the Outdoor Unit base valves.
a. Increase capacity by 1% for each 2°
F increase in subcooling.
b. Decrease capacity by 1% for each 2°
F decrease in subcooling.
3. Maximum recommended condensing temperature is 140°
F.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
TC17B2421S
INDOOR COIL MODEL NO.
CF48CXA1
AIR TEMP.
ENTERING
OUTDOOR UNIT (°F)
ID CFM
600
800
1000
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
55
T.C.
22.1
24.3
24.4
26.6
28.8
23.8
25.3
25.2
27.5
29.0
25.5
26.3
26.1
28.4
29.3
S.C.
21.2
19.0
16.1
16.0
12.8
22.9
21.7
18.1
17.8
13.5
24.7
24.4
20.0
19.5
14.2
KW
1.19
1.19
1.19
1.20
1.20
1.27
1.27
1.27
1.28
1.28
1.34
1.35
1.35
1.36
1.36
65
T.C.
21.6
23.5
23.4
25.8
28.2
23.3
24.4
24.3
26.7
28.7
25.0
25.4
25.2
27.6
29.2
S.C.
20.8
18.6
15.7
15.6
12.4
22.5
21.3
17.7
17.5
13.3
24.2
24.1
19.7
19.3
14.2
KW
1.32
1.32
1.33
1.33
1.33
1.40
1.41
1.40
1.41
1.41
1.47
1.49
1.48
1.48
1.49
75
T.C.
21.1
22.6
22.3
25.0
27.5
22.8
23.6
23.3
25.8
28.3
24.5
24.5
24.3
26.7
29.1
S.C.
20.4
18.3
15.3
15.2
11.9
22.0
21.0
17.3
17.2
13.1
23.7
23.7
19.4
19.1
14.3
KW
1.45
1.46
1.46
1.46
1.46
1.53
1.55
1.54
1.54
1.54
1.60
1.63
1.61
1.61
1.62
85
T.C.
20.3
21.7
21.5
23.8
26.4
21.9
22.6
22.3
24.6
27.1
23.6
23.5
23.2
25.4
27.7
S.C.
19.6
17.8
15.0
14.8
11.8
21.2
20.3
16.9
16.9
12.9
22.8
22.7
18.9
18.9
13.9
KW
1.62
1.62
1.62
1.63
1.63
1.70
1.71
1.70
1.70
1.71
1.77
1.79
1.78
1.78
1.79
95
T.C.
19.6
20.7
20.7
22.7
25.4
21.1
21.6
21.4
23.4
25.9
22.7
22.5
22.0
24.1
26.4
S.C.
18.9
17.4
14.7
14.5
11.6
20.4
19.5
16.5
16.6
12.6
21.9
21.7
18.4
18.7
13.6
KW
1.79
1.79
1.79
1.80
1.79
1.87
1.87
1.87
1.87
1.87
1.94
1.95
1.94
1.95
1.95
105
T.C.
18.6
19.6
19.5
21.4
23.9
20.0
20.4
20.1
22.1
24.5
21.5
21.2
20.7
22.8
25.1
S.C.
18.0
16.8
14.1
14.0
11.1
19.4
18.6
15.9
16.0
12.1
20.8
20.5
17.8
18.0
13.2
KW
2.04
2.04
2.04
2.05
2.05
2.12
2.12
2.12
2.12
2.13
2.20
2.20
2.20
2.20
2.21
115
T.C.
17.7
18.4
18.4
20.2
22.4
19.0
19.2
19.0
20.8
23.1
20.3
19.9
19.5
21.5
23.7
S.C.
17.1
16.2
13.6
13.5
10.5
18.3
17.8
15.4
15.4
11.7
19.6
19.3
17.2
17.3
12.8
KW
2.29
2.29
2.29
2.29
2.29
2.37
2.37
2.37
2.37
2.37
2.44
2.44
2.45
2.45
2.46
125
T.C.
16.7
17.3
17.2
19.0
21.0
17.9
18.0
17.8
19.6
21.7
19.1
18.7
18.3
20.1
22.4
S.C.
16.1
15.7
13.0
13.0
10.0
17.3
16.9
14.8
14.8
11.2
18.5
18.1
16.6
16.7
12.5
KW
2.54
2.54
2.54
2.54
2.54
2.61
2.61
2.62
2.61
2.62
2.69
2.69
2.69
2.69
2.71
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Green shaded cells are ACCA (TVA) conditions.
Blue shaded cells are AHRI conditions.