Johnson Controls Unitary Products
23
1109434-FTG-A-0714
COP equals MBH output divided by (total KW input x 3.412).
HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the total electric power input
during the same period.
— = Not Applicable.
MA Modular Air Handlers use Coil Only Ratings.
COP equals MBH output divided by (total KW input x 3.412).
HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the total electric power input
during the same period.
MA Modular Air Handlers use Coil Only Ratings.
PSC furnaces, such as the TG8S, TGLS, and TG9S, use Coil Only Ratings.
— = Not Applicable.
HL8B060F4(C)
MX16CN21
FC60C
1
1020
34.0
–
–
3.38
2
1600
48.0
32.4
9.75
3.76
2*
1020
46.0
29.4
9.05
3.12
AHE60D
–
1
1160
41.0
–
–
3.18
2
1835
58.0
38.0
9.35
3.78
2*
1160
59.0
37.2
9.00
2.96
AHV60D
–
1
1090
40.5
–
–
3.14
2
1635
57.5
38.0
9.30
3.64
2*
1090
58.5
37.0
9.15
2.90
MV20D
FC/MC60D
1
1160
41.0
–
–
3.10
2
1845
57.5
38.5
9.30
3.66
2*
1160
58.5
37.6
8.95
2.86
MV20D
FC/MC62D
1
1185
41.0
–
–
3.24
2
1845
58.0
38.0
9.40
3.80
2*
1185
59.0
37.0
9.20
3.00
MV20D
FC64D
1
1160
41.5
–
–
3.30
2
1855
58.5
38.5
9.35
3.86
2*
1160
59.5
37.6
9.25
3.06
1. Rated CFM same as for cooling.
2. Heating MBH based on AHRI standards of 70°F DB (Dry Bulb) entering indoor air, 72% RH (Relative Humidity) outdoor air with 25 feet of interconnecting pip-
ing and no supplemental electric heat operation.
* Notates “Hot Heat Pump” performance. These ratings are not AHRI listed.
HEATING CAPACITY - With Air Handler (Continued)
UNIT
MODEL
AIR HANDLER
MODEL
COIL
1
MODEL
HEATING
2
STAGE
RATED
CFM
NET MBH
HSPF
COP @ 47°F
47°F OD
17°F OD
18 SEER HP WITH AIR HANDLERS
HEATING CAPACITY - Upflow, Downflow, and Horizontal Furnaces and Coils (Coil Only Ratings)
UNIT
MODEL
COIL
1
MODEL
HEATING
2
STAGE
RATED
CFM
NET MBH
HSPF
COP @ 47°F
47°F OD
17°F OD
18 SEER HP COIL ONLY RATINGS
HL8B024F4(C)
FC/MC/PC48
1
600
19.70
–
–
3.24
2
800
24.60
17.50
8.5
3.54
2*
600
25.80
15.50
8.0
3.12
HL8B036F4(C)
FC/MC62
1
900
26.50
–
–
3.38
2
1200
36.50
24.60
9.2
3.88
2*
900
36.60
23.50
7.9
3.24
HL8B048F4(C)
FC/MC62
1
1200
35.20
–
–
3.32
2
1600
48.50
32.60
9.6
3.76
2*
1200
47.30
30.10
8.0
3.24
HL8B060F4(C)
FC/MC62
1
1350
42.50
–
–
3.14
2
1800
58.50
38.50
9.2
3.66
2*
1350
60.50
38.00
7.7
3.02
1. Rated CFM same as for cooling.
2. Heating MBH based on AHRI standards of 70°F DB (Dry Bulb) entering indoor air, 72% RH (Relative Humidity) outdoor air with 25 feet of interconnecting pip-
ing and no supplemental electric heat operation.
* Notates “Hot Heat Pump” performance. These ratings are not AHRI listed.