UNIT OPERATION

COOLING OPERATION

During cooling operation, the main outdoor control will receive a
communicated demand signal along with the current space
temperature and setpoint. The control algorithm will then utilize
these signals to communicate the proper compressor speed,
OD fan speed, and ID blower CFM to match system output for
the required space load.

MECHANICAL SPECIFICATIONS

MANUFACTURE AND CERTIFICATIONS

• Units shall be manufactured in an ISO 9001 certified facility.

• Units shall be certified by CSA to UL 1995 / CSA 22.2 and

performance certified to ANSI/AHRI Standard 210/240.

• Units shall be sound tested according to ANSI/AHRI Stan-

dard 270.

• Certified matched system ratings will be available for down-

load from the AHRI online directory at 

www.ahridirectory.org

.

• Unit packaging shall be marked, “Assembled in the USA”.

• Unit shall be labeled with the ENERGY STAR logo.

• Unit shall be recognized as ENERGY STAR Most Efficient.

(May apply only to select models in each series).

UNIT APPLICATION

• Units shall be approved for cooling operation between 35ºF

and 125ºF without modification.

• Units shall be approved for linesets up to 80 feet equivalent

length without modification.

• Units shall be approved for installation within 6 inches of a

flat vertical wall without modification, according to the
instructions in the technical literature.

• Units shall be certified to the 5th Edition (2014) of the Florida

Building Code for both Ground Mounted and Rooftop
Mounted applications up to 200 feet above grade with
approved mounting kit.

UNIT ACCESS

• Units shall have a removable fan guard that can be removed

independently of the top for interior access through the top of
the unit without damaging the coil.

• Units shall have two removable stamped steel coil guards for

exterior coil access.

• Units shall have a separate compartment for electrical con-

trols that can be accessed without disturbing the unit airflow.

• Units shall have a blockoff panel that can be removed to pro-

vide interior unit access through the side of the unit.

• Units shall have a removable blockoff panel and a swing

away removable electrical panel that provides sufficient inte-
rior unit access for removing the compressor through the
side of the unit.

UNIT CONSTRUCTION

• Units shall be shipped completely wired, piped and assem-

bled. Wiring pigtails shall be provided for field control wiring
connections. Service valves shall be provided for field refrig-
erant line connections.

• Units shall be factory leak checked, run tested, and shipped

with a holding charge of R-410A refrigerant.

• Unit cabinet components shall be G90 equivalent steel fin-

ished with powder-coat paint rated at a minimum of 1,000
hours under ASTM B117 testing.

• Unit shall be constructed with a composite base pan to pre-

vent corrosion and minimize noise and vibration.

• Units shall have a single corner post opposite the electrical

control box and two independently removable steel coil
guard panels to optimize cabinet strength and serviceability.

• Units shall have L-shaped stamped sheet metal coil guards

with extruded louvers for maximum panel durability and sys-
tem protection.

• Units shall have a factory installed filter-drier for faster instal-

lation and improved system reliability.

• Unit base valves shall be mounted diagonally on the unit

base pan with service ports that provide sufficient clearance
for low-loss hose fittings.

• Units shall be constructed with a high pressure switch and a

low pressure for system protection.

• Units shall be constructed with all badging and labels applied

at the factory.

UNIT COMPONENTS

• Compressor shall be hermetic with internal electrical over-

load protection and internal overpressure protection.

• Compressor shall be mounted on rubber vibration isolators

that do not require the removal of transportation clips or
brackets.

• Units shall be constructed using a scroll compressor paired

with an inverter drive.

• Condenser fan shall be direct drive with vertical air discharge

for low sound levels.

• Condenser fan blades shall be swept-wing to minimize

sound.

• Condenser fan motor shall be ECM construction with perma-

nently lubricated ball bearing motors approved for vertical
shaft applications.

• Condenser coil shall be air cooled and constructed of

enhanced aluminum fins mechanically bonded to internally
enhanced Ø 7mm copper tubing.

UNIT WARRANTIES

• Unit manufacturer shall provide a Limited Lifetime compres-

sor warranty with unit registration.

• Unit manufacturer shall provide a limited 5-Year parts war-

ranty extended to 10 years with registration.

Summary of Contents for ACCLIMATE AL21 Series

Page 1: ...ng high quality appearance Charge Smart A built in touch screen instantly displays the system overall condition including the system pressures and refrigerant charge without the need to attach additio...

Page 2: ...rranty when registered online within 90 days of installa tion Agency Listed Safety certified by CSA to UL 1995 CSA 22 2 Performance certified to ANSI AHRI Standard 210 240 in accordance with the Unita...

Page 3: ...2 Rows Deep 1 1 2 2 Fins Inch 22 22 18 18 Liquid Line Set OD Field Installed 3 8 3 8 3 8 3 8 Vapor Line Set OD Field Installed 3 3 4 3 4 7 8 7 8 Unit Charge Lbs Oz 4 7 8 7 6 14 9 15 1 Charge Per Foot...

Page 4: ...the system charge without attaching a separate manifold gauge set or temperature sensors 6 Permanently mark the unit data plate with the total amount of refrigerant in the system SYSTEM CHARGE FOR VA...

Page 5: ...r If OD Unit is Below ID Unit 24 3 8 3 4 80 feet 25 feet 25 feet 36 48 7 8 60 NOTICE Inverter Temperature Protection If excessive inverter temperatures are sensed the compressor speed capacity is redu...

Page 6: ...0 19 05 Low 475 14 20 11 30 35 70 AL21B4821S AVV49DE321 24 5 High 1550 45 50 34 40 20 00 13 00 Med 800 25 20 18 50 19 10 Low 525 14 90 11 50 36 20 AL21B4821S MVC16CN21 21 0 CM49CE3A1 High 1450 45 50 3...

Page 7: ...75 9 9 8 2 37 20 AL21B2421S LP9C060B12MP13C 17 5 CM25BE1A1 High 775 23 0 17 4 20 50 14 25 Med 475 13 8 10 8 19 05 Low 325 9 7 7 7 36 35 AL21B2421S LP9C080B12MP13C 17 5 CM25BE1A1 High 825 23 4 18 3 20...

Page 8: ...C080B12MP13C 17 5 CM37BE2A1 High 1250 34 6 26 4 19 00 12 20 Med 725 18 9 15 4 18 15 Low 475 11 0 9 6 33 05 AL21B3621S LP9C080C16MP13C 21 0 CM37CE2A1 High 1125 34 8 25 6 19 25 13 00 Med 650 18 6 14 8 1...

Page 9: ...LV120C20MP12C 21 0 CM49CE3A1 High 1525 45 5 33 2 19 50 12 50 Med 875 25 0 20 0 18 65 Low 675 14 4 11 1 34 05 AL21B4821S TP9C080C16MP13C 21 0 CM49CE3A1 High 1500 45 5 32 8 19 50 12 25 Med 775 25 0 19 1...

Page 10: ...0C20MP12C 21 0 CM61CE4A1 High 1675 52 5 37 6 19 75 12 50 Med 1100 30 2 24 6 18 95 Low 825 20 6 17 8 35 95 AL21B6021S TM8V120C20MP12C 21 0 CM61CE4A1 High 1675 52 5 37 6 19 75 12 50 Med 1100 30 2 24 6 1...

Page 11: ...0 6 17 8 35 95 AL21B6021S LP9C100C20MP13C 21 0 CM61CE4A1 High 1750 52 0 37 8 19 75 12 20 Med 1050 30 4 24 4 19 10 Low 700 20 4 16 3 37 05 AL21B6021S LP9C120D20MP13C 24 5 CM61DE4A1 High 1650 52 5 37 2...

Page 12: ...icient inte rior unit access for removing the compressor through the side of the unit UNIT CONSTRUCTION Units shall be shipped completely wired piped and assem bled Wiring pigtails shall be provided f...

Page 13: ...GHTXDWH ZDOO VXSSRUW 87 21 6SHFLDO FDUH PXVW EH WDNHQ WR DYRLG UHFLUFXODWLRQ RI GLVFKDUJH DLU WKURXJK RXWGRRU FRLO CAUTION Care must be taken to prevent ice from damaging the unit Damage may occur fro...

Page 14: ...080 5 1 7 1 81 76 127 OHDUDQFH EHWZHHQ WZR XQLWV PD EH UHGXFHG WR PLQLPXP SURYLGHG WKH VHUYLFH DFFHVV FOHDUDQFH LV LQFUHDVHG WR PLQLPXP DQG WKH FOHDUDQFH RQ HDFK UHPDLQLQJ VLGH LV PDLQWDLQHG DW PLQLP...

Page 15: ...6 14 6 15 3 15 5 17 0 19 1 KW 1 62 1 61 1 61 1 60 1 57 1 65 1 64 1 65 1 63 1 60 1 68 1 68 1 68 1 66 1 63 95 T C 20 0 21 5 21 5 24 7 27 1 20 8 22 4 22 5 25 3 28 3 21 6 23 2 23 4 25 9 29 5 S C 13 8 14...

Page 16: ...5 2 86 2 88 2 89 2 90 2 85 2 87 2 94 2 95 2 96 2 86 2 87 105 T C 30 1 31 8 32 6 35 8 40 4 31 4 32 9 34 2 39 1 43 8 32 7 33 9 35 7 42 4 47 3 S C 20 5 21 4 21 7 24 0 26 6 21 3 22 0 22 2 25 4 28 6 22 1 2...

Page 17: ...3 29 3 29 4 32 3 38 3 29 4 29 9 29 9 32 9 37 6 30 5 30 4 30 3 33 4 36 9 KW 4 58 4 60 4 60 4 65 4 72 4 67 4 68 4 68 4 73 4 79 4 76 4 77 4 76 4 82 4 85 115 T C 41 3 43 0 42 7 46 9 52 4 42 7 43 5 43 8 4...

Page 18: ...56 4 60 4 59 4 62 4 62 4 65 4 69 4 69 4 71 4 71 4 75 4 79 95 T C 51 3 53 9 54 8 60 2 65 5 53 3 55 3 55 8 61 1 66 9 55 3 56 6 56 7 61 9 68 2 S C 35 9 37 9 37 9 41 7 45 9 37 1 38 8 38 7 42 5 46 8 38 2...