Vacuum Regulator for Chlorine Gas
C 2700-V
Operating Instructions
BA-21210-02-V05
9 Shutdown
9.1 Short-term shutdown
Perform the following working steps:
1.
Close the chlorine container valves.
2.
Use the injector to suction off the remaining chlorine.
3.
Switch off the injector.
Chlorinator shut down for the short term.
9.2 Long-term shutdown
Precondition for action:
The chlorine gas container valves were closed.
The remaining chlorine was suctioned off using the injector.
The injector was switched off.
Perform the following working steps:
1.
Run the chlorinator for approximately five minutes with nitrogen or
dry compressed air.
2.
Close all the connections to protect the lines and devices from
humidity and dirt.
Chlorinator shut down for the long term.
9.3 Disposal of the old device
Before the disposal of the old device, clean off the remaining chlo-
rine by rinsing it with nitrogen or air.
The device must be disposed of in accordance with applicable local
laws and regulations. It should not be disposed of as domestic
waste!
As the disposal regulations may differ from country to country, please
consult your supplier if necessary.
Before commissioning after longer breaks in operation, minor
maintenance measures are recommended as a minimum
(see "Maintenance intervals" on page 22).