Lutron Electronics Co., Inc. 7200 Suter Road

Coopersburg, PA 18036-1299 USA

Customer Assistance  |  1.844.LUTRON1  

USA, Canada, and the Caribbean

  |  +1.888.235.2910 

Mexico

  |  +1.610.282.3800 

Others

  |  www.lutron.com

     

Part of the Vive System

Vive Integral Fixture Controls

Required Components 

For each fixture, you will need:

Vive Integral Fixture Control with Sensor 

(DFCSJ-OEM-OCC)

Vive Integral Fixture Control (RF only)  

(DFCSJ-OEM-RF)

Note:

 Neither Daylighting functionality nor occupancy 

sensing is available in the DFCSJ-OEM-RF

  Start Here

English

Important Notes: 

•  Use copper conductors only.

•  Check to see that the device type and rating is suitable for the application.

• 

DO NOT

 install if product has any visible damage.

•  If moisture or condensation is evident, allow the product to dry completely 

before installation.

•  Operate between 32 °F and 131 °F (0 °C and 55 °C), ambient.

•  0% to 90% humidity, non-condensing.

•  For indoor use only.

•  Sensor should be mounted to fixture in orientation that makes it parallel to 

the floor when fixture is installed in ceiling.

•  Clean only with soft, damp cloth, no chemical cleaners.

• 

DO NOT

 paint.

•  Intended for installation in fixture manufacturer’s facility only.

DFCSJ-OEM-OCC  

Vive Integral Fixture Control with Sensor

DFCSJ-OEM-RF  

Vive Integral Fixture Control (RF only)

2. Install Integral Fixture Control 

  •   Ensure knockout and adjacent surfaces are free from burrs, oil, chemicals, debris, etc.

  •   Do not push on the PIR lens or button to install the Fixture Control. Push on the center of the Fixture Control.

  •   Push firmly on the Fixture Control around the entire perimeter until it sits flush against the intended fixture mounting surface.  

A special tool from Lutron can be provided to facilitate installation.

  •   Do not fully enclose within the metal fixture.

3. Fixture Control Self-Test (REQUIRED)

The Vive integral fixture control supports a self-test mode in order to verify proper RF communication after 

being installed in a fixture. In case of self-test failure, the fixture must not be released to customers until the 

wiring and/or fixture construction is adjusted to improve RF performance until the fixture passes the self-test. 

See 

Wiring Best Practices

 section on the 

Vive Integral Fixture Controls App Note

 (048642) at  

www.lutron.com for details. 
Until one or more of the following conditions are met, the fixture control automatically enters self-test on 

power-up: 

  •  The fixture control has previously been powered continuously for more than 60 minutes. 

  •   The fixture control is associated to any other devices or a Vive system. 

Resetting the fixture control to factory defaults will reset the above conditions and re-enable automatic  

self-test entry.

The Fixture Control Self-Test is conducted as follows: 

   1.  While the test is in progress, the status LED alternates between green and red. During the test, the Vive 

integral fixture control will not respond to button presses or commands from other Lutron  

Clear Connect devices.

   2. Fixture will turn ON to full intensity for 5 seconds and then will turn OFF for 5 seconds. 

   3. Once the self-test is complete: 

 

 a.  If the fixture passes, the status LED blinks green twice, repeating every 2 seconds, and the fixture will 

turn ON. 

 

 b.  If the fixture fails, the status LED blinks red twice, repeating every 2 seconds, and the fixture will  

remain OFF. 

   4. To exit the self-test mode after completion, press the button or wait 5 minutes to exit automatically.

Note:

 Do NOT disconnect power to the fixture until the pass/fail determination has been made. 

4. Basic Functionality End-of-Line Test

   1. Provide power to the fixture.

   2. Fixture will go to the driver’s previous light level.

   3.  Press the button to toggle the load state. Light will fade to ON (or OFF) over 1 second. Green LED  

will stay lit for 2 seconds after releasing the button.

   4.  Toggle the load again (if necessary) to ensure the lights are on. This will make sure the lights turn ON when 

power is applied the next time (at job site).

   5. Remove power.

1. Connect Wires using Diagrams Below

  •   Vive Integral Fixture control contains two 18 AWG (0.75 mm

2

), solid copper wires.

For more information, see  
www.lutron.com/TechnicalDocumentLibrary/3691039.pdf
www.lutron.com/TechnicalDocumentLibrary/048642.pdf 
www.lutron.com/TechnicalDocumentLibrary/ApNote106.pdf

Please read before installing

+

One Fixture Control 

At least one EcoSystem Fixture Control digital link interface (DFC-OEM-DBI)

OR

+

At least one driver with self-powered DALI link  

(see 3691039 or 048642 on www.lutron.com for list)

9.5 – 20.5 V

-

250 mA max

041600 

Rev. B

04/2018

*

   For set-up, programming, and 

troubleshooting with a Vive system, 

please refer to the installation 

instructions included with the Vive hub 

or at www.lutron.com

Vive Integral Fixture Controls 

Controls up to 4 drivers (IEC 60929 Annex E.2 requires each driver to limit the sink/
source current draw to 2.0 mA maximum). See wiring diagrams for more details.

Default Functionality

Fixture Controls

Auto On level:

 

DFCSJ-OEM-OCC only

  

(not applicable for DFCSJ-OEM-RF)
Varies with ambient light level when occupancy is triggered 
(e.g., 100% for a dark room, 10% for a bright room).

Timeout period:

 15 minutes

 

Driver with self-powered DALI link

EcoSystem driver

OR

Fixture Control  

digital link interface

FCC information and IC information

This device complies with part 15 of the FCC Rules and Industry Canada 

license-exempt RSS standard(s). Operation is subject to the following 

two conditions: (1) This device may not cause interference, and (2) this 

device must accept any interference, including interference that may 

cause undesired operation. Modifications not expressly approved by 

Lutron Electronics Co., Inc. could void the user’s authority to operate this 

equipment.

NOTE:

 This equipment has been tested and found to comply with 

the limits for a Class B digital device, pursuant to part 15 of the FCC 

Rules. These limits are designed to provide reasonable protection 

against harmful interference in a residential installation. This equipment 

generates, uses and can radiate radio frequency energy and, if not 

installed and used in accordance with the instructions, may cause 

harmful interference to radio communications. However, there is no 

guarantee that interference will not occur in a particular installation. If 

this equipment does cause harmful interference to radio or television 

reception, which can be determined by turning the equipment off and on, 

the user is encouraged to try to correct the interference by one or more 

of the following measures:

•  Re-orient or relocate the receiving antenna.

•  Increase the separation between the equipment and receiver.

•   Connect the equipment into an outlet on a circuit different from that to 

which the receiver is connected.

LED/Daylight sensor lens 

PIR lens

Button

LED lens 
Button

 

   

   

120 – 277 V

~

120 – 277 V

~

Fixture Control  

digital link interface

EcoSystem driver

Driver with self-powered DALI link

Vive Integral  
Fixture Control

Vive Integral Fixture Controls with 
EcoSystem or DALI Driver*

Fixture Control with Driver with  
Self-powered DALI Link

E1

E2

120 – 277 V

~

E1
E2

SR+/DALI+ 
SR-/DALI- 

120 – 277 V

~

EcoSystem driver

Vive Integral  
Fixture Control

Driver

Maximum Number per 

Fixture Control

Philips

R

 SR driver

2

Osram

R

 DEXAL

T

 

driver

3

Driver

Maximum Number 

per Fixture Control

EcoSystem driver

4

For applications that require more drivers than shown here,  
contact the driver manufacturer.

IEC SELV / NEC

R

 Class 2 

UL2043 Plenum Rated

Review the 

Vive Integral Fixture Controls App Note

 (048642) at www.lutron.com for Wiring 

and Fixture Construction Guidelines.

S+ 

S-

    

Notes:

1.  E- and E+ from the DFC-OEM-DBI can go to either the E1 or E2 terminal on the EcoSystem driver.  

2.  S- and S+ from the DFC-OEM-DBI can go to either wire from the Vive Integral Fixture Control.

*   Please see the 

Notes

 section for additional details

Note:

 When using multiple drivers with self-powered DALI link, SR+/

DEXAL+ from the drivers must be tied together and the SR-/DEXAL- 
from the drivers must be tied together. Do NOT mix “+” and “-“ when 
using multiple drivers.”