background image

®

Job Name:

Job Number:

Model Numbers:

Page

S P E C I F I C A T I O N   S U B M I T T A L

369656b   5   05.04.12

Occupant Sensors

ULOS-CIR Series

Sensors

Installation

Sensor Placement

Range Diagrams

• The occupant sensor must have an unobstructed view of the room. Do not mount behind or near tall 

cabinets, shelves, indirect hanging fixtures, etc.

• Do not place sensor within 6 ft (1.8 m) of air vents, air handlers, windows, fans, etc., as this may cause 

false triggering.

• Closely follow the diagrams shown concerning major and minor motion coverage. The sensor can detect 

major motion (such as a person taking a half-step) at a greater distance than it can detect minor motion 
(such as writing or typing at a desk).

• May not detect occupancy with no significant difference between ambient and body temperatures.

Major motion detection

Minor motion detection

6.5 ft (1.9 m)

12 ft (3.7 m)

LOS-CIR-1500

LOS-CIR-450

12 ft (3.7 m)

22 ft (6.7 m)

Summary of Contents for ULOS-CIR Series

Page 1: ...ive infrared PIR sensor Passive infrared sensing Reliable motion detection with high error immunity Snap locks to ceiling mounted cover plate Non Volatile Memory settings saved in protected memory are...

Page 2: ...n detected Housing Rugged high impact injection molded plastic Color coded leads 6 in 15 cm Power Operating voltage 20 24 V PELV Class 2 USA low voltage Operating current 33 mA nominal Control output...

Page 3: ...rfaced to lighting control system see below Power Supply Options Lutron Lighting Control System Power Pack Required Digital microWATTTM No EcoSystem No GRAFIK 5000 6000 7000TM No when used with seeTou...

Page 4: ...Red Red 1 to 3 Sensors with Power Pack Switching Multiple Loads with Auxiliary Power Packs Hot Neutral Hot Manual switch off optional Lighting Load Lighting Load Power Pack Auxiliary Power Pack Red R...

Page 5: ...ft 1 8 m of air vents air handlers windows fans etc as this may cause false triggering Closely follow the diagrams shown concerning major and minor motion coverage The sensor can detect major motion...

Page 6: ...to cover plate Drill through ceiling tile with assembly using cutter end of the threaded mounting post Secure with washer and nut Cutter end Mounting to Non Standard Ceiling or Fixture Mount twist loc...

Page 7: ...e 8 minute setting Factory Settings 12 o clock Full CCW Auto Manual Threshold LED Motion Indicator Reset Learned Settings Strong Airflow Compensation Over Doorway Installation Timer Adjust Auto Sensit...

Reviews: