background image

®

Job Name:

Job Number:

Model Numbers:

Page

S P E C I F I C A T I O N   S U B M I T T A L

369656b   3   05.04.12

Occupant Sensors

ULOS-CIR Series

Sensors

Wiring

Single Sensor to System

2 or More Sensors to System

Lighting 
control 
system

Red (+20 - 24 V

)

Blue (signal)

Black (common)

Red (+20 - 24 V

)

Blue (signal)

Black (common)

Lighting 
control 
system

To additional 

sensors, maximum 

determined by 

lighting controller

Note: Power pack may be required when interfaced to lighting control system; see below.

Power Supply Options

Lutron Lighting Control System 

Power Pack Required?

Digital microWATT

TM

 No

EcoSystem

®

 No

GRAFIK 5000 / 6000 / 7000

TM

 

 No, when used with seeTouch

®

 wallstations with occupant sensor 

connections.

GRAFIK Eye

®

 3000 / 4000 

Yes

HomeWorks

®

 Yes

LCP128

TM

 

 No, when used with seeTouch

®

 wallstations with occupant sensor 

connections.

microWATT

®

 No

RadioRA

®

 Yes

RadioTouch

®

 No

Softswitch128

®

 

 No, when used with seeTouch

®

 wallstations with occupant sensor 

connections.

NOTE:

 Power Pack may be required for more than one Occupant Sensor. Consult factory for multiple 

sensor requirements.

Summary of Contents for ULOS-CIR Series

Page 1: ...ive infrared PIR sensor Passive infrared sensing Reliable motion detection with high error immunity Snap locks to ceiling mounted cover plate Non Volatile Memory settings saved in protected memory are...

Page 2: ...n detected Housing Rugged high impact injection molded plastic Color coded leads 6 in 15 cm Power Operating voltage 20 24 V PELV Class 2 USA low voltage Operating current 33 mA nominal Control output...

Page 3: ...rfaced to lighting control system see below Power Supply Options Lutron Lighting Control System Power Pack Required Digital microWATTTM No EcoSystem No GRAFIK 5000 6000 7000TM No when used with seeTou...

Page 4: ...Red Red 1 to 3 Sensors with Power Pack Switching Multiple Loads with Auxiliary Power Packs Hot Neutral Hot Manual switch off optional Lighting Load Lighting Load Power Pack Auxiliary Power Pack Red R...

Page 5: ...ft 1 8 m of air vents air handlers windows fans etc as this may cause false triggering Closely follow the diagrams shown concerning major and minor motion coverage The sensor can detect major motion...

Page 6: ...to cover plate Drill through ceiling tile with assembly using cutter end of the threaded mounting post Secure with washer and nut Cutter end Mounting to Non Standard Ceiling or Fixture Mount twist loc...

Page 7: ...e 8 minute setting Factory Settings 12 o clock Full CCW Auto Manual Threshold LED Motion Indicator Reset Learned Settings Strong Airflow Compensation Over Doorway Installation Timer Adjust Auto Sensit...

Reviews: