S p e c i f i c at i o n   S u b m i t ta l

page

Job Name:

Job Number:

Model Numbers:

QS System

QSE-CI-NWK-E

Control Interface

369373b   3   06.21.12

2.47

(62.7)

3.75

(95.3)

4.26

(108.2)

5.26

(133.6)

1.06

(26.9)

Mounting holes

Terminal 

blocks 

on this side

LEDs and addressing 

switches on this side

Dimensions

Dimensions are in inches (mm)

0.34 

(8.6) dia.

0.18 

(4.6) dia.

0.18 

(4.6) dia.

0.25 

(6.4)

#6 or #8 (M3 or M4) 

screw recommended

Mounting Hole Detail

Mounting Options

Mounting Methods

Mount where terminal blocks, switches, and LEDs are 

accessible. Strip 

4

 in (10 mm) of insulation from 

wires. Each data link terminal will accept up to two 

 

18 AWG (1.0 mm

2

) wires. Connect wiring as shown 

on the Wiring page. Choose from the following 

mounting methods:

1: Direct Wall Mounting

Mount the control interface directly on a wall, as 

shown in Mounting Methods at right, using screws 

(not included). When mounting, provide sufficient 

space for connecting cables.

2: Rack Mounting

Place the unit can in the LUT-19AV-1U AV rack using 

screws (not included). The LUT-19AV-1U will hold up 

to four units.

3: Enclosed Wall Mounting

If conduit is desired for wiring, use the 

 

LUT-5x10-ENC to mount one unit.

lut-19aV-1u

2

lut-5x10-enc

5.26

4.26

3.75

2.50

1.06

control interface

Wall

1

3

Summary of Contents for QSE-CI-NWK-E

Page 1: ...I NWK E control interfaces are allowed per QS link The QSE CI NWK E is Quantum compatible Refer to the Quantum System Specification Sheet for compatibility details Compatible Components The following devices are compatible with the QS link For more information on each refer to www lutron com qs GRAFIK Eye QS control units seeTouch QS wallstations Sivoia QS shades QS Interfaces contact closure Ethe...

Page 2: ... commands please refer to the protocol document on the accompanying CD also available at www lutron com RS232 Connection Standard 9 pin female serial connector on interface 50 ft 15 m maximum serial cable length Dip switches are set at factory all Off Dip switches are used to set RS232 baud rate DIP Switch Settings for RS232 Baud Rate 115200 default 38400 19200 9600 Ethernet Connection Standard CA...

Page 3: ...le Strip 4 in 10 mm of insulation from wires Each data link terminal will accept up to two 18 AWG 1 0 mm2 wires Connect wiring as shown on the Wiring page Choose from the following mounting methods 1 Direct Wall Mounting Mount the control interface directly on a wall as shown in Mounting Methods at right using screws not included When mounting provide sufficient space for connecting cables 2 Rack ...

Page 4: ...Locations LED and DIP Switch Locations Ethernet Link to PC or AV Equipment Female 9 pin RS232 Link to PC or AV Equipment QS Link to other wired QS system Devices To external power supply DIP Switches LED 1 Power LED 2 Ethernet Activity LED 3 Unused LED 4 RS232 Link Tx LED 5 RS232 Link Rx LED 6 QS Link Tx LED 7 QS Link Rx 1 2 3 4 5 6 7 ...

Page 5: ... L N 4 3 2 1 To additional QS devices RS232 Cable 50 ft 15 m max Ethernet Link CAT5 Cable 328 ft 100 m max COM TxD RxD RS232 Link To PC or AV Equipment Rear View of GRAFIK Eye QS Control Unit To external power supply QS Link 1 Common 2 Power 3 MUX 4 MUX See next page Do not connect Pin 2 if using external power supply QS Link Ethernet Link Wiring Standard CAT5 cable connects QSE CI NWK E Interface...

Page 6: ...erminal accepts up to two 18 AWG 1 0 mm wires Total length of control link must not exceed 2000 ft 610 m Typical Wire Sizes See QS Link Wire Sizes table Connect the terminal 1 3 and 4 connections to all control units wallstations and control interfaces in the QS system For terminal 2 connectivity see below 4 3 2 1 Lutron Cable See QS Link Wire Sizes table QSPS P1 1 50 provides up to 8 power draw u...