S p e c i f i c at i o n   S u b m i t ta l

page

Job Name:

Job Number:

Model Numbers:

QS System

QSE-CI-NWK-E

Control Interface

369373b   2   06.21.12

Specifications

Power

• IEC PELV/NEC

®

 Class 2

• Operating voltage: 12–24 V   65 mA

QS Link Limits

• The QS wired communications link is limited to 

100 devices and 100 zones. Each QSE-CI-NWK-E 

control interface counts as 2 devices and 2 zones.

• Each QSE-CI-NWK-E control interface consumes 

 

2 power draw units (PDU) on the QS link. Refer 

to the QS Link Power Draw Units Specification 

Submittal (Lutron PN 369405, at www.lutron.com) 

for more information.

• The maximum wiring length for the QS link is 2000 ft 

(610 m).

Environment

• 32 to 104 °F (0 to 40 °C). 

• Relative humidity less than 90% non-condensing.

Integration Features

• Monitoring: Current scene, zone level, button 

presses, shade group levels.

• Control: Scene selection, scene lockout, zone 

lockout, sequencing, zone raise/lower, master raise/

lower, set shade group level, simulate button press/

release.

For the full list of features and commands, please 

refer to the protocol document on the 

accompanying CD, also available at  

www.lutron.com.

RS232 Connection

• Standard 9-pin female serial connector on interface. 

• 50 ft (15 m) maximum serial cable length.

• Dip switches are set at factory, all Off. 

• Dip switches are used to set RS232 baud rate:

DIP Switch Settings for RS232 Baud Rate

115200 (default)

38400

19200

9600

 

Ethernet Connection

• Standard CAT5 (or better) cable, 328 ft (100 m) 

maximum, connects the QSE-CI-NWK-E interface to a 

PC or other Ethernet source.

• Supports MDI/MDIX auto-crossover (no crossover 

cable needed).

• Auto-negotiation of 10 or 100 Mbps speed and full- or 

half-duplex operation.

• Default IP address is 192.168.250.1. Can be changed 

using the Lutron DeviceIP tool located on the 

accompanying CD.

Note: 

Either the RS232 or the Ethernet can be used, 

but not both.

115200

38400

19200

9600

1   2   3   4   5   6   7   8

1   2   3   4   5   6   7   8

1   2   3   4   5   6   7   8

1   2   3   4   5   6   7   8

115200

38400

19200

9600

1   2   3   4   5   6   7   8

1   2   3   4   5   6   7   8

1   2   3   4   5   6   7   8

1   2   3   4   5   6   7   8

115200

38400

19200

9600

1   2   3   4   5   6   7   8

1   2   3   4   5   6   7   8

1   2   3   4   5   6   7   8

1   2   3   4   5   6   7   8

115200

38400

19200

9600

1   2   3   4   5   6   7   8

1   2   3   4   5   6   7   8

1   2   3   4   5   6   7   8

1   2   3   4   5   6   7   8

Summary of Contents for QSE-CI-NWK-E

Page 1: ...I NWK E control interfaces are allowed per QS link The QSE CI NWK E is Quantum compatible Refer to the Quantum System Specification Sheet for compatibility details Compatible Components The following devices are compatible with the QS link For more information on each refer to www lutron com qs GRAFIK Eye QS control units seeTouch QS wallstations Sivoia QS shades QS Interfaces contact closure Ethe...

Page 2: ... commands please refer to the protocol document on the accompanying CD also available at www lutron com RS232 Connection Standard 9 pin female serial connector on interface 50 ft 15 m maximum serial cable length Dip switches are set at factory all Off Dip switches are used to set RS232 baud rate DIP Switch Settings for RS232 Baud Rate 115200 default 38400 19200 9600 Ethernet Connection Standard CA...

Page 3: ...le Strip 4 in 10 mm of insulation from wires Each data link terminal will accept up to two 18 AWG 1 0 mm2 wires Connect wiring as shown on the Wiring page Choose from the following mounting methods 1 Direct Wall Mounting Mount the control interface directly on a wall as shown in Mounting Methods at right using screws not included When mounting provide sufficient space for connecting cables 2 Rack ...

Page 4: ...Locations LED and DIP Switch Locations Ethernet Link to PC or AV Equipment Female 9 pin RS232 Link to PC or AV Equipment QS Link to other wired QS system Devices To external power supply DIP Switches LED 1 Power LED 2 Ethernet Activity LED 3 Unused LED 4 RS232 Link Tx LED 5 RS232 Link Rx LED 6 QS Link Tx LED 7 QS Link Rx 1 2 3 4 5 6 7 ...

Page 5: ... L N 4 3 2 1 To additional QS devices RS232 Cable 50 ft 15 m max Ethernet Link CAT5 Cable 328 ft 100 m max COM TxD RxD RS232 Link To PC or AV Equipment Rear View of GRAFIK Eye QS Control Unit To external power supply QS Link 1 Common 2 Power 3 MUX 4 MUX See next page Do not connect Pin 2 if using external power supply QS Link Ethernet Link Wiring Standard CAT5 cable connects QSE CI NWK E Interface...

Page 6: ...erminal accepts up to two 18 AWG 1 0 mm wires Total length of control link must not exceed 2000 ft 610 m Typical Wire Sizes See QS Link Wire Sizes table Connect the terminal 1 3 and 4 connections to all control units wallstations and control interfaces in the QS system For terminal 2 connectivity see below 4 3 2 1 Lutron Cable See QS Link Wire Sizes table QSPS P1 1 50 provides up to 8 power draw u...

Reviews: