369883d   13   04.19.17

Field Adjustment Knob

The Field Adjustment Knob is located on the side of the Hi-lume Premier 0.1% Constant Voltage Driver (L3D0) 
enclosure. This feature enables the customer to tune the lowest light output achieved during normal operation. An 
example of this scenario is shown in the image below. Adjusting the Field Adjustment Knob of the lower light 
output driver minimizes the light output difference and sets the low-end light level at 0.1%. This feature 

only needs

 

to be used in cases of mismatched loads that are separately controlled by 2 or more units.

The Field Adjustment Knob cannot fix light level mismatch among loads on the same driver. For example, two 
homeruns of different wattage. For increasing the minimum light output of all the drivers in a space, please use  
the control's low-end trim feature. Using the Field Adjustment Knob for this purpose will degrade On / Off transition 
performance.

Figure 1: Cove Lighting with Mismatched Light Output at Low-End Due to Installation Variability

lutron.com

lutron.com

lutron.com

2 W Load  

0.1% dim level

96 W Load  

< 0.1% dim level

Figure 2: Cove Lighting After the Use of the Field Adjustment Knob Eliminates Mismatch without Costly Re-wiring

2 W Load  

0.1% dim level

96 W Load  

0.1% dim level

Steps:
1.   Set the control to low-end and turn all knobs fully 

counter-clockwise

2.  Identify the driver with the lowest light output
3.   Turn the knob clockwise until the light output 

matches the brightest driver

4.   Repeat steps 2-3 until all drivers match in low-end 

light output

13

Summary of Contents for L3D0-96W24V-U

Page 1: ...with EcoSystem controls PowPak with EcoSystem dimming modules PowPak with EcoSystem wireless fixture controls and Quantum systems allowing for integration into a planned or existing EcoSystem lightin...

Page 2: ...stant voltage at high end Output Load Range 2 W to 96 W at high end PWM dimming frequency meets IEEE1789 at all dim levels Power Factor 0 90 at maximum power Total Harmonic Distortion THD 20 at maximu...

Page 3: ...o 12 AWG 0 50 mm2 to 2 5 mm2 Maximum wire length between the LED driver and the start of the linear strip for different wire sizes is listed below The table below can be used independently of the line...

Page 4: ...Specifications are subject to change without notice Output Voltage vs Output Power Output Power W Output Power W Output Power W Output Voltage V THD Efficiency 0 0 10 10 20 20 30 30 40 40 50 50 60 60...

Page 5: ...on de R glage pour utilisation en chantier Hi lume Premier 0 1 Suitable for damp locations Convient aux emplacements humides Use 20 12 AWG wire only Utiliser un fil de 0 50 2 5 mm seulement WARNING Sh...

Page 6: ...tural Dimming 369883d 6 04 19 17 Mounting Options1 2 1 Any other mounting configuration will require additional mechanical support Improper installation may result in hazards to personnel or property...

Page 7: ...EcoSystem links are wired as Class 2 or between the EcoSystem control and output terminals Option 2 when the EcoSystem links are wired as Class 1 For 3 wire control barrier could be placed in either l...

Page 8: ...M5 Hi lume Premier 0 1 WARNING Shock hazard May result in serious injury or death Disconnect power before opening top lid servicing or installing AVERTISSEMENT Danger d lectrocution Peut causer de gra...

Page 9: ...14 Maestro Wireless dimmer MRF2 F6AN DV 1 6 1 14 RadioRA 2 dimmer RRD F6AN DV 1 6 1 14 Dual voltage 3 wire dimmer 21 4 HomeWorks QS dimmer HQRD F6AN DV 1 6 1 14 Fluorescent 3 wire LED 3 wire 21 4 Inte...

Page 10: ...EcoSystem link GRAFIK Eye QS unit with EcoSystem QSGRJ _E QSGR _E 9 009 or higher 64 per EcoSystem link Quantum Light Management Hub QP2 _P_C 3 2 or higher4 64 per EcoSystem link HomeWorks QS with Ec...

Page 11: ...ase consult load manufacturer best practices for any additional consideration in load installation When connecting several LED light homeruns ensure that the wire lengths and wattages match as closely...

Page 12: ...r wire per terminal Make sure that the supply breaker to the drivers and EcoSystem Digital Link Supply is OFF when wiring E1 and E2 terminals of the drivers can be daisy chained as shown to the right...

Page 13: ...ustment Knob cannot fix light level mismatch among loads on the same driver For example two homeruns of different wattage For increasing the minimum light output of all the drivers in a space please u...

Page 14: ...quipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is...

Reviews: