8
DALI Touchpanel, Manual © 2017/01/16, Lunatone Industrielle Elektronik GmbH
For each Button effective range, ON/OFF-Command and Dim-Mode can be configured.
Parameter Dim Mode:
Dim-Mode
Short Press
Long Press
Toggle ON/OFF
Toggles between ON and OFF
Command
Dim Up Only
ignored
Switch On if required, Dim Up
Dim Up and ON for Short Press
On-Cmd
Switch On if required, Dim Up
Dim Down Only
ignored
Dim Down
Dim Down and OFF for Short Press
Off-Cmd
Dim Down
Toggle UP/DOWN
ignored
Alternating Dim Up/Down
Toggle UP/DOWN and ON/OFF for
Shortpress
Alternating ON- and OFF-Cmd
Alternating Dim Up/Down
Example1:
•
Effective Range: Group G2
•
Dim Mode: toggle ON/OFF
•
ON/OFF-Cmd: On – GoTo Scene 1, Off – GoTo Scene 1
On each press the command l GOTO SCENE 1 is sent to group 2.
Example 2:
•
Effective Range: short addressA03
•
Dim Mode: ToggleUp/Down and On/Off for Short Press
•
ON/OFF-Cmd: On-Recall Max, Off-Off
On short press alternating on/off using cmds RECALL MAX and OFF. On long press alternating dim up
and down. This way it is possible to switch on/off and dim A03 by one button only.
2.2
Configuation of DALI Touch with firmware version =4.8)
The configuration site is divided in several tabs. For each layout and for the general settings tabs are
available.
The menu on the left provides general functions: display of the existing layouts, creating new layouts,
deleting existing layout, adding pics for layouts etc. Furthermore the calibration algorithm of the
touch panel can be started.
On the top of each site general device information is shown (manufacturer, article name, article
number, serial number, firmware version etc.)