ND30PNET-09 -
User's Manual
40
4046
RW
-1440..0..1440
[
‰]
Alarm output 1 - upper value of switching condition 2 of
input nominal range
1100
4047
RW
0..3600 s
Alarm output 1
– delay of condition 2 activation
0
4048
RW
0..3600 s
Alarm output 1
– delay of condition 2 deactivation
0
4049
RW
0..3600 s
Alarm output 1
– lock of condition 2 reactivation
0
4050
RW
0.1
Alarm output 1
– signaling condition 2 occurrence
0
4051
RW
Reserved
4052
RW
0.1..43
Alarm output 1 - quantity for condition 3 (c3)
(code acc. to table 8)
38
4053
RW
0..9
Alarm output 1
– type for condition 3: 0 – n_on, 1 – noFF,
2
– on, 3 – oFF, 4 – H_on, 5 – HoFF, 6 – 3non, 7 – 3noF,
8
– 3_on, 9– 3_oF
0
4054
RW
-1440..0..1440
[
‰]
Alarm output 1 - lower value of switching condition 3 of
input nominal range
900
4055
RW
-1440..0..1440
[
‰]
Alarm output 1 - upper value of switching condition 3 of
input nominal range
1100
4056
RW
0..3600 s
Alarm output 1
– delay of condition 3 activation
0
4057
RW
0..3600 s
Alarm output 1
– delay of condition 3 deactivation
0
4058
RW
0..3600 s
Alarm output 1
– lock of condition 2 reactivation
0
4059
RW
0.1
Alarm output 1
– signaling condition 2 occurrence
0
4060
RW
Reserved
4061
RW
0...4
Alarm output 2- logic actions of conditions 1, 2, 3
0
– C1
1
– C1 v C2 v C3
2
– C1
C2
C3
3
– C1
C2 v C3
4
– (C1 v C2
C3
0
4062
RW
0.1
Alarm output 2- state of relay at alarm occurrence: 0 - relay off
1 - relay on
1
4063
RW
0.1
Alarm output 2- lock of alarm deactivation
0
4064
RW
0.1
Alarm output 2- signaling of alarm occurrence
0
4065
RW
0.1..43
Alarm output 2 - quantity for condition 1 (c1)
(code acc. to table 8)
38
4066
RW
0..9
Alarm output 2
– type for condition 1: 0 – n_on, 1 – noFF, 2
– on, 3 – oFF, 4 – H_on, 5 – HoFF, 6 – 3non, 7 – 3noF,
8
– 3_on, 9 – 3_oF
0
4067
RW
-1440..0..1440
[
‰]
Alarm output 2 - lower value of switching condition 1 of
input nominal range
900
4068
RW
-1440..0..1440
[
‰]
Alarm output 2 - upper value of switching condition 1 of
input nominal range
1100
4069
RW
0..3600 s
Alarm output 2
– delay of condition 1 activation
0
4070
RW
0..3600 s
Alarm output 2
– delay of condition 1 deactivation
0
4071
RW
0..3600 s
Alarm output 2
– lock of condition 1 reactivation
0
4072
RW
0.1
Alarm output 2
– signaling condition 1 occurrence
0
4073
RW
Reserved
4074
RW
0.1..43
Alarm output 2 - quantity for condition 2 (c2) (code acc. to
table 8)
38
4075
RW
0..9
Alarm output 2
– type for condition 2: 0 – n_on, 1 – noFF, 2
– on, 3 – oFF, 4 – H_on, 5 – HoFF, 6 – 3non, 7 – 3noF,
8
– 3_on, 9 – 3_oF
0