ND30PNET-09 -
User's Manual
39
4016
RW
0.1
Synchronization with real time clock
0 - no synchronization
1 - synchronization with the clock
1
4017
RW
Reserved
4018
RW
Reserved
4019
RW
Reserved
4020
RW
Leads resistance value for input T1 x 100
0
4021
RW
Leads resistance value for input T2 x 100
0
4022
RW
Reserved
4023
RW
Reserved
4024
RW
0…4
Resetting energy meters:
0
– no changes, 1- reset active energies,
2
– reset reactive energies, 3 – reset apparent energies, 4 –
reset all energies
0
4025
RW
0.1
Resetting averaged parameters P
Demand, S Demand, I
Demand
0
4026
RW
0.1
Resetting min, max
0
4027
RW
0.1
Resetting alarm signaling maintenance
0
4028
RW
Reserved
4029
RW
Reserved
4030
RW
0...4
Alarm output 1- logic actions of conditions 1, 2, 3
0
– C1
1
– C1 v C2 v C3
2
– C1
C2
C3
3
– C1
C2 v C3
4
– (C1 v C2
C3
0
4031
RW
0.1
Alarm output 1- state of relay at alarm occurrence: 0 - relay off
1 - relay on
1
4032
RW
0.1
Alarm output 1- lock of alarm deactivation
0
4033
RW
0.1
Alarm output 1- signaling of alarm occurrence
0
4034
RW
0.1..43
Alarm output 1 - quantity for condition 1 (c1)
(code acc. to table 8)
38
4035
RW
0..9
Alarm output 1
– type for condition 1: 0 – n_on, 1 – noFF, 2
– on, 3 – oFF, 4 – H_on, 5 – HoFF, 6 – 3non, 7 – 3noF,
8
– 3_on, 9 – 3_oF
0
4036
RW
-
1440..0..1440
[
‰]
Alarm output 1 - lower value of switching condition 1 of
input nominal range
900
4037
RW
-1440..0..1440
[
‰]
Alarm output 1 - upper value of switching condition 1 of
input nominal range
1100
4038
RW
0..3600 s
Alarm output 1
– delay of condition 1 activation
0
4039
RW
0..3600 s
Alarm output 1
– delay of condition 1 deactivation
0
4040
RW
0..3600 s
Alarm output 1
– lock of condition 1 reactivation
0
4041
RW
0.1
Alarm output 1
– signaling condition 1 occurrence
0
4042
RW
Reserved
4043
RW
0.1..43
Alarm output 1 - quantity for condition 2 (c2) (code acc. to table 8)
38
4044
RW
0..9
Alarm output 1
– type for condition 2: 0 – n_on, 1 – noFF, 2
– on, 3 – oFF, 4 – H_on, 5 – HoFF, 6 – 3non, 7 – 3noF,
8
– 3_on, 9 – 3_oF
0
4045
RW
-1440..0..1440
[
‰]
Alarm output 1 - lower value of switching condition 2 of
input nominal range
900