Lumatek CONTROL PANEL PLUS 2.0 Manual Download Page 10

Press [OK] to enter Home screen

Press [<]or[>] to ZONE A and [OK] to enter

In ZONE A Press [<]or[>] to Power and [^]or[v] to select required power output (light 

intensity) and Press [OK] to action and save.

Selecting 0% will switch lamps Off.

Repeat to set up Zone B.

Note! If controller is disconnected from power supply; any set parameter values 

and Time/Date will be saved.

Press [<]or[>] to Hour and Minute settings and [^]or[v] to set time in hours and 

minutes and [OK] to save.

Press [>] to Power setting and [^]or[v] to set power output and [OK] to save.

To pre-set switch Off; set Power to 0%.

2

6.  CONTROLLER LED INDICATOR

LED ON

: Normal status (temperature probe is working normally)

LED OFF

: Temperature probe cable not connected correctly or temperature control fail.

LED SLOW FLASH

: High temperature 

auto-dim

 threshold; ballast will now dim to reduce temperature.

LED FAST FLASH

: High temperature 

auto-shutdown

; ballast will switch off.

LED ON

: Lamp is on

LED OFF

: Lamp is off

The same reading as 1

The same reading as 2

0-10V LED ON only: 

0-10V analog signal 

to both Zones for LED drivers

RS485 LED ON only

RS485 digital signal to both 

Zones for HID

Both 0-10V & RS485 LED ON

Zone A is 0-10V for LED drivers and 

Zone B is RS585 for HID ballasts.

1

3

4

5

6

6.  Real time On/Off switching and adjusting light intensity

7.  LED FAILURE INDICATOR ON ELECTRONIC BALLAST

Note!

 If 

controller not connected;

 the power output LED will go On normally and in 

the event of any failure; the LED above highest power output setting will flash. See 

table below to decode fault.

If 

controller connected

; the 

‘controller 

‘ LED on electronic ballast will turn 

On

and 

flash every 2 seconds; this means that the controller is working normally.If the 

ballast fails to receive signal from the controller (either because of poor signal 

cable connection or controller failure) the ‘controller’ LED on ballast will flash 

quickly (every 0.2 seconds). In the event of any other failure; the 

LED above 

highest power output setting on ballast will flash.

 See table below to decode fault.

Summary of Contents for CONTROL PANEL PLUS 2.0

Page 1: ...DUAL SIGNAL LIGHTING CONTROLLER FOR HID LED CONTROL PANEL PLUS MANUAL...

Page 2: ...eys 5 2 2 System settings 5 2 3 Setting signal protocol 5 2 4 Zone parameter settings 5 2 5 Setting pre set Switch ON OFF and light intensity times 5 2 6 Real time On Off switching and adjusting light...

Page 3: ...or up to 50 LED fixtures with analog 0 10V signal It is possible to use each Zone to control fixtures in two independent separate rooms or to control up to 400 fixtures in one room with two different...

Page 4: ...00W 630W 945W 50 100 475W 945W 1000W 60 115 600W 1150W 400 RS485 250W 315W 400W 600W 630W 1000W CONTROLLABLE LED DRIVER TYPE All Lumatek controllable LED drivers 200 RS485 100 0 10V 50 0 10V Adaptor 1...

Page 5: ...and may cause malfunctions in the connected equipment Doing so will void the warranty Warning Do not open or disassemble the controller it contains no serviceable parts Opening the controller will vo...

Page 6: ...res eg Zone A can be set to control 600W LED fixtures and Zone B set to control 465W or 1000W LED fixtures Note Each of the controller s two channels Zone A Zone B can control up to 50 LED fixtures It...

Page 7: ...you can continue to set up the controller Connect controller cable C D from Zone A B output port 3 to Signal In port on LED fixture 1 or ballast 1 IN port Warning The controller may only be connected...

Page 8: ...ed in Type in Zone A B page and W Watts when HID is selected Note LED driver power output is shown as a percentage of the driver s nominal power output eg 50 of a 1000W LED driver is 500W To set Time...

Page 9: ...nt crop damage In ZONE A Press or to Dim and or v to select required temperature to engage auto dim and Press OK to save In ZONE A Press or to Stop and or v to select required temperature to engage au...

Page 10: ...N Lamp is on LED OFF Lamp is off The same reading as 1 The same reading as 2 0 10V LED ON only 0 10V analog signal to both Zones for LED drivers RS485 LED ON only RS485 digital signal to both Zones fo...

Page 11: ...allasts are working together some units are working well but some fail to work Check control cable connections Check if the ballast is faulty Disconnect and reconnect control cable or replace cable Ch...

Page 12: ...ate of purchase If the product shows any defects within this period and that defect is not due to user error or improper use Lumatek Ltd shall at its discretion either replace or repair the product us...

Page 13: ...E A LIGHT SIGNAL OUTPUT INCREASE OR DECREASE PARAMETERS RIGHT SHIFT OK AND SAVE SET SIGNAL PROTOCOL PAGE UP OR PAGE DOWN POWER ADAPTOR INPUT ZONE B THERMO SENSOR INPUT ZONE A THERMO SENSOR INPUT ZONE...

Reviews: