Lucent Technologies 1200A 24V ECS Battery Plant J85500E-2
Issue 7 October 1998
Engineering, Planning, and Ordering 3 - 19
For nontypical ECS configurations where the supplementary
bays are not located adjacent to the initial bay, battery cables
must be engineered.
Five sizes of plug-in circuit breakers are available for dc
distribution overcurrent protection. The ratings of these circuit
breakers are 10, 20, 30, 45 and 60 amperes. Two screw panel
mount breakers with current ratings of 100 and 225 amperes are
also available. The breaker rating for a given circuit is selected
by the criteria covered in paragraph “Overcurrent Protection.”
Table 3-E: Lug And Hardware Ordering Codes
Available Double Hole Terminal Lugs
STR
Class B
Flex Class
1
WP-91412
List
Comcode
Bolt Size
Centers
Die
10
8
8
6
4
2
-
1/0
-
2/0
-
4/0
10
8
8
6
4
-
2
1/0
-
2/0
-
4/0
73
52
75
3
5
54
8
56
13
13
20
59
158
405356171
405348178
406021626
405347519
405347576
40534 8202
405347683
405348228
405347758
405347758
405347857
405348251
406434175
10
10
1/4
1/4
1/4
1/4
1/4
5/16
5/16
5/16
5/16
5/16
5/16
5/8
5/8
5/8
5/8
5/8
5/8
5/8
1.0
1.0
1.0
1.0
1.0
1.0
R5473
Red
Red
Blue
Grey
Brown
Green
Pink
Black
Black
Orange
Purple
Yellow
Available Single Hole Terminal Lugs
STR
Class B
Flex Class
1
WP-91412
List
Comcode
Bolt Size
Die
10
8
8
6
4
2
-
1/0
-
2/0
-
4/0
10
8
8
6
4
-
2
1/0
-
2/0
-
4/0
93
1
74
2
4
53
7
55
10
10
17
58
76
406338145
405347402
405356189
405307436
405347543
40534 8186
405347659
405348210
405347717
405347717
405347790
405348244
406021741
10
10
1/4
1/4
1/4
1/4
1/4
5/16
5/16
5/16
5/16
5/16
5/16
R5473
Red
Red
Blue
Grey
Brown
Green
Pink
Black
Black
Orange
Purple
Yellow