5.2 Mounting dimensions
Drawings showing all required mounting and liquid connection dimen-
sions are available for download on alfa.luvegroup.com.
5.3 Feet dimensions detail
Feet dimensions are identical for all models.
Avoid any lateral torque on the feet when fixing the unit.
Fixing holes can be used to fix the unit to the ground or to a beam structure and for the installation
of vibration dampers.
5.4 Concrete mounting base
To avoid oxidation of the equipment feet, it
is strongly recommended to mount the heat
exchanger on concrete mounting bases. One
base for each foot. Base minimum dimensions
are 100 mm height and 260 mm width.
5.5 Expansion joints
Alfa LU-VE recommends the installation of
expansion joints on both inlet and outlet con-
nections. Expansion joints are elastic elements
which, if properly installed, absorb the thermal
expansions of the tubing. Expansion joints are
also helpful in order to reduce vibrations in the
piping.
Dimensional drawings
2280
80
20.5
160
Fixing hole
& Vibration damper
160
80
1740