Platform for two to six units
Number of fan pairs
2, 3
4, 5, 6
7, 8, 9
H ≥
(N-1)/2
(N-1)/1.2
N-1
d ≥
L/2
L/2
L/2
h ≤
(N-1)/2
(N-1)/1.2
N-1
N= number of units on the platform.
All three conditions (H, d, h) shall be met. Contact Alfa LU-VE in case a different lay out is required.
Special care should be taken in particular circumstances, such as:
• When installation site is exposed to strong winds.
• When walls with different configuration or heights than the ones shown in the previous pictures
are present.
• When more than 6 units are installed on a single platform.
• When severe environmental loads (e.g. earthquakes) are likely to affect to the unit.
In these cases contact your local Alfa LU-VE representative for support.
5.8 Electrical connections
The following data determine which connection diagram is to be selected and respected for electri-
cal installation:
• Heat exchanger model indication
• Fan motor type
• Electrical options
Electrical connection diagrams are available for download on
alfa.luvegroup.com. When in doubt always contact your local Alfa LU-VE
representative for assistance.