7. Function List
7-7
LED
display
Parameter
name
Min/Max
range
Description
Factory
defaults
Adjustable
during run
Page
F59
[Stall
prevention
select]
0/7
This parameter stops accelerating
during acceleration, decelerating
during constant speed run and stops
decelerating during deceleration.
0
X
During
Decelerati-
on
During
constant
speed
During
Acceleratio
-n
Bit 2
Bit 1
Bit 0
0
-
-
-
1
-
-
2
-
-
3
-
4
-
-
5
-
6
-
7
F60
[Stall
prevention
level]
30/150
[%]
This parameter sets the amount of
current to activate stall prevention
function during Accel, constant or
Decel run.
The set value is the percentage of
the H33- [Motor rated current].