Chapter 10. Installation and Wiring
10-6
10.2 Wiring
It describes the wiring that you should know when installing the XGT Panel.
10.2.1 Power wiring
XGT Panel is divided into the DC product and the AC product.
Remark
(1) Affix the brackets on four sides of the product to prevent ingress by water and dust.
(2) Affix the brackets top to bottom and right to left to prevent gaps.
(3) Align the brackets vertically with the panel. The screw torque of the brackets is 6.42kgf/cm. The screw torque may vary
by the quality of the panel, but it should follow the standard screw torque value for a bolt. If you apply excessive force
when affixing the brackets, the XGT Panel can be damaged. This may result in touch screen errors or weaken the
protection against water and dust ingress.
(4) After mounting the XGT Panel on the panel, remove the screen protection film. Touch screen errors may result if the film
is not removed. To protect the screen, use the exclusive protection sheet. To purchase a protection sheet, contact the
agency or a sales office.
Power
Name
DC 24V
iXP50-TTA/DC
DC 12/24V
iXP70-TTA/DC
iXP80-TTA/DC
iXP90-TTA/DC
AC 100-240V
iXP70-TTA/AC
iXP80-TTA/AC
iXP90-TTA/AC
►
If AC power is applied into the product for DC power, It may cause damage or fire.
Be careful of connection.
►
‘/DC’ is the product which use DC 12/24V, and ‘/AC’ is the product which use AC 100-240V.
When using the product, Please check the label in the back of the product
.
Warning