Chapter 10. Installation and Wiring
10-8
Remark
(1) Use a regulated power supply transformer when the power fluctuation is bigger than the standard.
(2) If electromagnetic interference is experienced or expected use an insulation transformer to protect the XGT panel
from interference.
Separate the XGT Panel power from the I/O device and main circuit device.
Remark
(1) Separate the XGT Panel power supply cable from the main circuit cable (high voltage and current) and
input/output cable. Maintain a minimum separation of 100mm between cables.
AC power connection
Main Power
XGT Panel power
I/O power
Main circuit power
I/O device
Main circuit device
Constant
Voltage
Transformer
AC Power
100-240 V
FG