Sphensor
–
User manual
LSI LASTEM SRL
INSTUM_04291
Pag. 17 / 32
Being equipped with only the radio communication part, the setting of the repeaters operation is done by
modifying a subset of the parameters available for the sensor configuration.
3.4
Sphensor Gateway configuration
Once the sensors and any repeaters have been configured, proceed to the configuration of Sphensor Ga-
teway.
From the Sphensor Manager main window:
1.
Choose
Config
from the
Hub
menu to open the Sphensor Gateway configuration dialog.
2.
Select the current configuration (
IsCurrent
= True) and choose
Clone
.
3.
In the
GENERAL
tab you can assign a description to the configuration.
4.
The
ENDPOINTS
tab displays the MQTT servers configured in the device. In the figure are represented
two servers, one local (
localhost
) and one called
LSI Lastem
, both configured to receive the data
unencrypted and to have control of Sphensor Gateway.
For each server you can configure:
➢
EnableControl
: if checked, enables Sphensor Gateway control and then its reconfiguration by
the software on PC. If the option is not enabled, you cannot send reconfiguration commands
to Sphensor Gateway via the specified broker.