3. Parameters - overview

Parameter

Description

How to set

H30

Motor Power in kW

Set to match motor nameplate - eg. 0.75 for 0.75kW, 1.5 for 1.5kW etc.

H31

Number of Motor Poles

Set to match motor nameplate - eg. 2700-3000RPM = 2, 1350-1500RPM = 4 etc.

H32

Motor Slip in Hz

Calculate: (Motor Frequency - ((Motor RPM x Poles) / 120))

H33

Motor Full Load Current in Amps

Set to match motor nameplate - eg. 4.7

H34

Motor No-Load Current in Amps

See section 5 for details of how to correctly set this value.

Parameter

Description

How to set

drv

Run/Stop Command Source

Set to

for Run/Stop buttons on the iC5.

0

Frq

Speed Command Source

Set to

to use the dial on the iC5.

2

Parameter

Description

How to set

F21

Max Output Frequency in Hz

Default is 60. Change to 50 for 50Hz motor.

F22

Base Frequency

Default is 60. Change to 50 for 50Hz motor.

F24

Enable Max/Min Frequency

Default is 0 (off). Set to 1 to enable parameters F25 and F26 for future use.

F27

Torque Boost

Default is 0 (off). Set to 1 to improve starting Torque.

F50

Thermal Overload

Default is 0 (off). Set to 1 to enable Thermal Overload Protection.

The iC5 contains a number of settings which
can be changed to tailor it for use in a wide
range of applications. These settings are
known as parameters.

Parameters are typically referred to by code or
number (eg. H21 = Max Output Frequency)
with a description available in the manual.

The parameters contain critical information
essential to the correct operation of the iC5.
Therefore, they should at least be checked by
the user before it is operated for the first time.

The parameters listed in section 4 are intended
to provide a starting point to allow for basic
operation of the iC5 Inverter.

4.3 Parameters in Function Group 2 - “H”

Press left/right to find H0 then up/down to find parameter number

4. Parameters to set before use

See section 6 for an explanation of Parameter Groups

and to learn how to set a parameter value.

Set the following parameters to allow the iC5 to
run in standard mode with Run, Stop and
Speed Control from the integral keypad.

If any of the parameters have been changed
previously, follow the procedure in section 12
to reset the iC5 to Factory Defaults.

4.2 Parameters in Function Group 1 - “F”

Press left/right to find F0 then up/down to find parameter number

4.1 Parameters in the Drive Group

Press left/right to find 0.0 then up/down to find parameter number

Summary of Contents for iC5 Series

Page 1: ...ded by the manufacturer It is provided as a basic introduction to the product for Inverter Drive Supermarket customers It should not be used as a replacement for the manual issued by the manufacturer v1 2 20110316 This product is not a safety device All safety considerations including but not limited to Emergency Stop provision should be assessed separately and are outside the scope of this guide ...

Page 2: ...Page 4 Page 5 Page 6 Page 8 Page 9 Page 10 Page 11 Page 12 Page 13 Contents Power and Motor Connections Motor Connections Star and Delta Parameters Overview Parameters to set before use How to set Motor no load current H34 How to Operate the Inverter How to enable Sensorless Vector Mode How to connect and configure a Potentiometer for remote speed control How to connect and configure a Run Stop sw...

Page 3: ... is based on 1 5kW and 2 2kW models The terminal layout for 0 37kW and 0 75kW models is slightly different The smaller green earth terminals are not part of the main termal block The order of the three phases determines the direction the motor turns Important Do NOT connect Neutral to the terminal marked N Use screened SY cable between the Inverter and Motor to minimise electromagnetic interferenc...

Page 4: ...fety purposes Star shown opposite is the default configuration for new motors and is sometimes known as two at one side Only two links are required for Star Double up the links if changing from Delta to allow the motor to be changed to back in future The order of the three phases determines the direction the motor turns Note that the cable screen and earth are connected together at the earth termi...

Page 5: ... Boost Default is 0 off Set to 1 to improve starting Torque F50 Thermal Overload Default is 0 off Set to 1 to enable Thermal Overload Protection The iC5 contains a number of settings which can be changed to tailor it for use in a wide range of applications These settings are known as parameters Parameters are typically referred to by code or number eg H21 Max Output Frequency with a description av...

Page 6: ...ouple the motor from the machine before beginning 5 1 2 Use the navigation pad to locate the CUr parameter Make a note of this value It is Motor no load current inAmps and must be set in parameter H34 Press the down arrow on the navigation pad until CUr is displayed as shown opposite CUr is a read only parameter which displays output current inAmps Press the navigation pad to select Cur The output...

Page 7: ...igation pad to move between parameters within the selected parameter group 6 3 Press the navigation pad to edit a parameter Once the desired parameter is shown on the display in this case H33 press the navigation pad to select it In some cases it is possible to accidentally press an arrow key instead of the navigation pad In this case ensure you re select parameter H33 before attempting to press t...

Page 8: ...PNP RUN STOP RST FWD REV min max 6 5 Press the navigation pad to save changes Press the navigation pad again to confirm Once the value of H33 has been changed to 4 7 press the navigation pad to save changes The display will then flash indicating that the change needs to be confirmed Press the navigation pad again to confirm the change or wait to cancel the change and return to the edit screen in t...

Page 9: ... Hz 7 2 Press the green Run button to start the motor The green Run button will start the motor The motor will accelerate to the speed set by the dial see step 1 above in the time defined by the ACC parameter found in the Drive parameter group Motor speed can be changed whilst the motor is running by turning the dial clockwise faster or anti clockwise slower When the motor is running the FWD light...

Page 10: ...o operate in Sensorless Vector mode This can improve motor performance without requiring a separate feedback device Sensorless Vector mode operates in the same way as VxF but performs a number of calculations to improve low speed torque This requires an ID run during which the Inverter runs the motor for approx 1 minute at various speeds to gather the necessary data Decouple the motor from the mac...

Page 11: ...ating should be used The number of turns depends on the application but both single turn and ten turn Potentiometers are available from The Inverter Drive Supermarket at InverterDrive com 10kOhm 9 2 Connecting the Potentiometer A wiring diagram is shown in the illustration opposite The most important connection at the Potentiometer end is the centre terminal or wiper The wiper will output a variab...

Page 12: ... Inverter can no longer be used Important P1 refers to the P1 I O terminal and NOT the P1 power terminal 1 2 1 10 2 Connecting the Switch Digital Input A wiring diagram is shown in the illustration opposite The CM terminal output is 24V DC when the Inverter is connected to a power supply This is provided as a 24V output only and has no other function When the P1 terminal receives 24V ie when the c...

Page 13: ...the functionality added in section 10 to include Run Forward Reverse as well as Stop Important P1 and P2 refer to the P1 P2 I O terminals NOT P1 P2 power terminals 11 2 Connecting the Switch Digital Inputs A wiring diagram is shown in the illustration opposite The switch used is a DPDT centre off type The CM terminal provides a 24V DC output as described in section 10 When the switch is moved to t...

Page 14: ... off the iC5 for 60 seconds before switching back on 12 2 Press the navigation pad to change the value of parameter H93 Once the display shows H93 press the navigation pad to select the parameter and edit it s value The display will show the default value of 0 12 3 Press the up arrow on the navigation pad to change the value from 0 to 1 Press the up arrow on the navigation pad once to change the v...

Page 15: ...roduced by The Inverter Drive Supermarket Ltd All content including but not limited to graphics text and procedures copyright The Inverter Drive Supermarket and must not be reproduced or altered without prior written permission LS Industrial Systems SV iC5 ...

Reviews: