4) Setpoint no. 22. The adjustment frequency in seconds of the PID controller.
3.10 Factory settings
The ES10 can be reset to factory settings in setpoint menu no. 24. Set the value to
”1” and
press enter. The unit will now return to factory settings and restart. See section 4 for factory
setting values.
4 Setpoint menu table
Setpoint
number
Display text
Description
Min
value
Max
value
Factory
settings
1
Pressure day
Flow day
Setpoint day mode
operation
0Pa
0.00m/s
5000Pa
50.00m/s
200Pa
2.00m/s
2
Pressure night
Flow night
Setpoint night mode
operation
0Pa
0.00m/s
5000Pa
50.00m/s
150Pa
1.50m/s
3
Pressure max
Flow max
Setpoint max mode
operation
0Pa
0.00m/s
5000Pa
50.00m/s
400Pa
4.00m/s
4
Pressu error +/-
Flow error +/-
Pressure/flow +/-
threshold before alarm
activation
0Pa
0.00m/s
1000Pa
10.00m/s
100Pa
1.00m/s
5
Time delay alarm
Time delay for
pressure/flow before
alarm is activated.
0sek
1000sek
300sek
6
Temp comp.
Outdoor temperature
compensation OFF or
ON
0=OFF
1=ON
0=OFF
7
Temp comp max.
Max temperature when
compensation is
activated
-10.0
C 15.0
C
5.0
C
8
Temp comp min
Min temperature when
compensation is at max.
-25.0
C 0.0
C
-10.0
C
9
Temp pres reduce
Temp flow reduce
Pressure/flow value to be
compensated for
0Pa
0.00m/s
500Pa
5.00m/s
50Pa
0.50m/s
10
Motor out max.
Max voltage on 0-10VDC
motor output
50%
100%
100%
11
Motor out min.
Min voltage on 0-10VDC
motor output
0%
50%
0%
12
Sensor max.
Pressure/flow value
which the sensor
measures at output of
10VDC
0Pa
0.00m/s
5000Pa
50.00m/s
500Pa
5.00m/s
13
Sensor V 0Pa/ms
Voltage of pressure/flow
sensor at 0Pa or 0m/s
0.0V
10.0V
0.0V
14
Inverted output
0-10VDC motor output in
inverted operation
0=OFF
1=ON
0=OFF
15
Pressure/flow
Setting of control of
pressure or flow
0=Pres
1=Flow
0=Pres