LS Control ES 10 Manual Download Page 8

10VDC output during operation. This setpoint is adjustable from 0% to 50% (0%=0,0VDC, 
50%=5,0VDC). 
 
 
Inverted operation. It is possible to invert the 0-10VDC output on the ES10, i.e. when the 
requirement for air volume is low, the 0-10VDC output voltage is increased instead of 
decreased. This is set in the setpoint menu no. 14. The value 

”0” = Normal output, the value 

”1” = Inverted output.  
 
Frequency converter / Triac controller. The choice of frequency converter or triac controller 
as motor controller is set in the setpoint menu no. 16. The value 

”0” = Frequency converter, 

the value 

”1” = Triac controller. If ”triac controller” is selected in setpoint menu no. 16, the 

setpoint menu no. 17 must be adjusted. In this setpoint the size of the sudden pressure 
increases that may occur in the ventilation system are to be set. This value is adjustable 
from 0 to 1000Pa or from 0.00m/s to 10.00m/s. 
    

3.7 Pressure or flow transducer 

 
Standard. The ES10 is able to control air pressure or air flow by means of the associated air 
pressure or air flow transducer. This transducer is fitted on clamp 5 (0VDC), clamp 6 
(+24VDC), and clamp 7 (0-10VCD pressure/air flow input). 
An optional pressure transducer ES11 is available as accessory to the ES10. If the ES11 is 
used, it is not necessary to adjust the setpoints concerning the pressure sensor as these 
have been set at the factory. The measuring range of the ES11 is 0Pa to 500Pa. 
 
Other transducers. If a different air pressure or air flow transducer is chosen, the setpoint 
menu no. 12 and no. 13 are to be set. In setpoint menu no. 12, the pressure or airflow which 
the chosen sensor measures, is adjusted when the sensor output is 10VDC. This setpoint is 
adjustable from 0Pa to 5000Pa or from 0.00m/s to 50.00m/s. Example: If a pressure 
transducer at an output of 10VDC measures 500Pa, then 500Pa must be entered in the 
setpoint menu no. 12.  
In setpoint menu no. 13, the voltage output of the air pressure or the air flow transducer at 
0Pa respectively 0m/s is adjusted. This setpoint is adjustable from 0.0V to 10.0V. 
Example: If a pressure transducer measures 0Pa at 1.0V. This value must be entered in 
setpoint menu no. 13.  
  

3.8 Language 

 
The menu language is available in Danish and English. The language is set in setpoint 
menu no. 18. Value 

”0” = Danish and value ”1” = English.    

 

3.9 PID controller 

 
Air pressure or air flow adjustment is controlled by a PID controller. The PID controller is 
equipped with 4 setpoints in the setpoint menu.  
 

1)  Setpoint no. 19. PID KP. The amplification of the PID controller. 
2)  Setpoint no. 20. PID TI. The integration time of the PID controller. 
3)  Setpoint no. 21. PID H. The sampling time of the PID controller. 

Summary of Contents for ES 10

Page 1: ...Industrivej 12 Gelsted DK 4160 Herlufmagle Tel 45 5550 5550 Fax 45 5550 2265 www lscontrol dk lsc lscontrol dk ES 10 Constant pressure or flow regulator ...

Page 2: ... 3 3 Functions 4 3 1 Main menu 4 3 2 Setpoint menu 4 3 4 Alarm control 5 3 5 Outdoor temperature compensation 7 4 Setpoint menu table 9 5 Mounting 10 6 Technical specifications 11 7 Product codes 12 8 Applicable standards 12 9 Document versions 12 ...

Page 3: ...3 different operation modes and related setpoints are available day operation mode night operation mode and max operation mode The ES10 may be equipped with a temperature sensor for outdoor temperature compensation The ES10 is compatible with all pressure and flow sensors with a 0 10VDC output signal As standard the ES10 is equipped with a voltage free contact for connection to the BMS system or o...

Page 4: ...ired The display shows MENU enter passw Use arrow up and arrow down to select the first numbers in the password and the enter button to continue to the next figure When the figure has been entered press the enter button to access the setpoint menu The password is 1234 The first line in the display will show Edit setp no 1 Edit setpoint The individual setpoint number is selected by pressing arrow u...

Page 5: ...justment mode or from 0 00m s to 50 00m s in air flow adjustment mode The motor relay cl16 17 is closed and the motor output cl12 13 receives a voltage signal In night mode the alarm surveillance is active See alarm description in section 3 4 4 Max mode The ES10 is adjusting according to the max mode setpoint This is set in setpoint menu no 3 This setpoint is adjustable from 0Pa to 5000Pa in air p...

Page 6: ...ted in setpoint menu no 5 The time can be set from 0 to 1000 sec If the pressure air flow falls below this treshold again the alarm will automatically be deactivated See example in fig 3 1 3 Pressure air flow alarm below setpoint If the measured pressure flow falls below the desired regulation setpoint less an alarm threshold pressure air flow setpoint alarm threshold the following alarm will be d...

Page 7: ...to 500Pa or from 0m s to 5 00m s Note that the outdoor temperature compensation only is active in day mode and max mode and not in night mode See fig 3 2 Fig 3 2 3 6 Motor control Connection The ES10 has a 0 10VDC output cl 12 13 for control of a frequency converter or a triac controller Furthermore the ES10 has a operation relay cl 16 17 which will be closed when the unit is in day night or max m...

Page 8: ...11 is used it is not necessary to adjust the setpoints concerning the pressure sensor as these have been set at the factory The measuring range of the ES11 is 0Pa to 500Pa Other transducers If a different air pressure or air flow transducer is chosen the setpoint menu no 12 and no 13 are to be set In setpoint menu no 12 the pressure or airflow which the chosen sensor measures is adjusted when the ...

Page 9: ...00m s 1000Pa 10 00m s 100Pa 1 00m s 5 Time delay alarm Time delay for pressure flow before alarm is activated 0sek 1000sek 300sek 6 Temp comp Outdoor temperature compensation OFF or ON 0 OFF 1 ON 0 OFF 7 Temp comp max Max temperature when compensation is activated 10 0 C 15 0 C 5 0 C 8 Temp comp min Min temperature when compensation is at max 25 0 C 0 0 C 10 0 C 9 Temp pres reduce Temp flow reduce...

Page 10: ...mounting according to applicable mounting regulations The ES10 is to mounted on a flat and stable surface on which the ES10 is fixed with screws in the 4 corner holes The ES10 is not to be mounted on moving or vibrating surfaces Cables are run through cable gland and tightened Accessory The ES11 pressure transduer is to be mounted according to applicable regulations The ES11 must be mounted on a f...

Page 11: ...0mA Cl12 13 On off input Pull down input broken off Cl10 11 Full speed input Pull down input shortened Fullsp Cl8 9 Pressure input 0 10VDC in 4 7Kohm 10bit Cl7 5 24VDC supply 24VDC out 50 20 Max 80mA Cl6 7 NTC temperature sensor 22Kohm NTC 0 5 C 40 to 60 C Max 20 meters cable not shielded Cl3 4 Night set back input Pull down input shortened night C1 2 Pres transducer ES11 0 500Pa 15VDC to 38VDC 15...

Page 12: ...30 Accessory ES11 pressure transducer 0 500Pa Product code 40740 8 Applicable standards EN 61000 6 1 and EN 61000 6 2 Electromagnetic Compatability EMC EN 60 60730 1 The Low Voltage Directive 9 Document versions Ver 0 4 26 9 2006 MJ Ver 1 0 JEH 13 04 2011 Ver 1 1 JEH 14 01 2016 ...