3 Functions
3.1 Main menu
The main menu in the display consists of two lines. In
the first line the following information is shown: Current
operation mode (Stop, Day, Night, Max) and whether
outdoor temperature compensation is active (Temp
Komp).
In the second line the following information is shown:
1) Current pressure (Pa) or current air velocity (m/s).
2)
Press ”arrow down” and the outdoor temperature will be shown, if this sensor is mounted.
If an outdoor temperature sensor is not mounted, -40.0
C will be displayed.
3)
Press ”arrow down” again and the current motor speed in % will be shown
(0%=0VDC og 100%=10VDC).
4)
Press ”arrow down” again and ”MENU press enter” will be shown. Press “enter” until the
setpoint menu appears. See description below.
3.2 Setpoint menu
The individual setpoints are explained in section 3.3 and onwards and in the setpoint table
in section 4.
Access to menu.
Press ”arrow down” several time in the main menu, until ”MENU press
enter” appears in the display. Keep the “enter” button down until the setpoint menu appears.
A password is required. The display shows
”MENU enter passw”. Use ”arrow up” and ”arrow
down” to select the first numbers in the password, and the ”enter” button to continue to the
next figure.
When the figure has been entered, press the “enter” button to access the
setpoint menu. The password is
”1234”. The first line in the display will show:
”Edit setp no: 1”.
Edit setpoint. The individual setpoint number is selected by pressin
g ”arrow up” and ”arrow
down”. Press enter to access and edit the required setpoint. Now the display shows
”Setpoint no: ?” and ”Value: ?”. The values of the individual setpoints are changed by
pressing ”arrow up” and ”arrow down”.
Save setpoint.
Press “enter” to save the new value and return to the setpoint menu again. If
“esc” is activated, the new value will not be saved.
Exit from menu.
To exit the setpoint menu, press ”arrow up” until ”Edit setp no: 0”, ”Enter for
exit” is displayed. Now press ”enter” to exit the setpoint menu.
Timeout from menu. If none of the buttons are activated, the program will automatically exit
the setpoint menu after 30 seconds. Note that the pressure/flow regulation is not active
when the setpoint menu is active.
3.3 Air pressure / adjustment of air flow
It is possible to set the ES10 to maintain a constant air pressure or a constant air flow.