Setpoint
number
Display text
Description
Min
value
Max
value
Factory
settings
16
Freqconver/Triac
Setting of frequency
converter or triac
controller
0=
Frequency
converter
1=Triac
0=
Frequency
converter
17
Triac press
Triac flow
Pressure/flow value
indicating a sudden
pressure/flow change
0Pa
0.00m/s
1000Pa
10.00m/s
50Pa
0.50m/s
18
Language 0:DK
1:UK
Language choice for
menus
0=DK
1=UK
0=DK
19
PID kp
PID controller
amplification
0
250
10
20
PID ti
PID controller integration
time
0
4000
3000
21
PID h
PID controller sampling
frequency
0
2000
600
22
PID period
PID controller is called
every time the set value
is reached
0.0sec
25.0sec
1.0sec
23
Max. in invert
Max mode input inverted
function
0=OFF
1=ON
0=OFF
24
Factory setting
Reset to factory setting
0=OFF
1=Reset
0=OFF
5 Mounting
The ES10 constant pressure/air flow regulator is to be mounting according to applicable
mounting regulations.
The ES10 is to mounted on a flat and stable surface on which the ES10 is fixed with screws
in the 4 corner holes. The ES10 is not to be mounted on moving or vibrating surfaces.
Cables are run through cable gland and tightened.
Accessory
: The ES11 pressure transduer is to be mounted according to applicable
regulations. The ES11 must be mounted on a flat and stable surface on which the ES11 is
fixed with screws in the 4 corner holes. The ES11 is not to be mounted on moving or
vibrating surfaces.
The cable is run trough the cable gland and tightened.
The air connection piece is mounted on the ventilation duct in the measuring point. The air
connection piece is connected via a piece of tubing, for + or
– connection piece on the ES11
pressure transducer for measuring of either positive or negative pressure.
If the ES11 is mounted in a pressure neutral area, it is not necessary to connect the other
connection piece on the ES11. In this case a piece of tubing must be run to the neutral
pressure area.