Protect Switch 400V motors
Version:
3.0 | 14.02.2021
instruction manual | 1162723-00000
page
13
from
29
5.1.2.1.2 Safe inputs
On the second address (the address is described as Y below) the node has
four inputs that are used in the function as follows:
Function
Bit (input)
Motor overload tripped
Y.0 = 1
Temperature switch, motor
Y.1 = 1
Automatic (auto) mode*
1
Y.2 = 1 | Y.3 = 0
Manual (man) mode*
1
Y.2 = 0 | Y.3 = 1
Motor off*
1
Y.2 = 0 | Y.3 = 0
Current monitoring
*2
Y.2 = 1 | Y.3 = 0
*1 optional with knob-operated control
*2 optional with current monitoring
*1 and *2 in combination not possible
5.1.2.1.3 Diagnosis
The node has a diagnostic address. This is exclusively used for parametrizing the AS-i node (the address is
described as P below).
The following settings can be made via the diagnostic address.
Diagnosis
Bit
Switches the clockwise and anti-clockwise function when release is given
P.0 = 1
Switches the clockwise function when release is given and X.0 (OUT1) = 1
Switches the anti-clockwise function when release is given and X.1 (OUT2) = 1
P.0 = 0
Release feedback for user via Y.3 (not used)
P.1 = 1
Y.3 Standard input (Manual operation via knob-operated control) *
1
P.1 = 0
*1 optional with knob-operated control
The diagnostic parameter settings are made exclusively via the safety monitor software (ASIMON360 from
B+W).