L-IP User Manual
62
LOYTEC
Version 6.1
LOYTEC electronics GmbH
including all required files. A file requestor dialog allows specifying the location where the
backup file shall be stored.
To restore the device settings, simply select a previously generated backup file in the
Restore Configuration
section of the page by clicking the button next to the
Filename
field. Then press the
Restore
button.
The backed up configuration data consists of:
Device settings (Passwords, IP settings, etc.),
CEA-709 commissioning information,
CEA-852 device and configuration server information (if enabled),
L-IP redundant configuration data (node list, parameters, etc).
Figure 52: Backup/Restore page.
Note:
Backups created with firmware versions prior to version 6.0 cannot be restored on
firmware versions 6.0 and up! Please make sure you re-create backups when upgrading the
firmware!
6.2.3 Port Configuration
This menu allows configuring the device’s communications ports. For each communication
port, which is available on the device and shown on the label (e.g., Port 1, Port 2 Ethernet),
a corresponding configuration tab is provided by the Web UI. An example is shown in
Figure 53. Each port tab contains a selection of available communication protocols. By
selecting a checkbox or radio button the various protocols can be enabled or disabled on the
communication port. Some ports allow exclusive protocol activation only, other ports (e.g.,
the Ethernet port) allow multiple protocols bound to that port.