Message display

Under  normal  operation,  the  temperature  of  the  probe  selected  by  P4  will  be
displayed, the following messages may also appear:

•Err 

Memory reading error.

•ErP 

Error of the probe not shown on the display.

•AH1 

Maximum temperature alarm, probe 1.

•AL1 

Minimum temperature alarm, probe 1.

•AH2 

Maximum temperature alarm, probe 2.

•AL2 

Minimum temperature alarm, probe 2.

•ooo 

Open probe.

• --- 

Shorted probe.

Pressing SET with UP it displays the probe not selected by P4.
When  the  probe  not  selected  by  P4  is  displayed,  it  alternates  its  value  with
message Sd1 or Sd2 depending if it is probe 1 or probe 2.
The display blinks when waiting for a value confirmation.

LED indications
Out1: 

Indicates relay 1 On or Off as per parameter H2. If H2=dir, with relay 1 On,

LED lit, if H2=inv, with relay 1 On, LED off. It blinks when SP1 is displayed.

Out2: 

Indicates relay 2 On or Off as per parameter H3. If H3=dir, with relay 2 On,

LED lit, if H3=inv, with relay 2 On, LED off. It blinks when SP2 is displayed.

Setting SP1 and SP2
• 

Press and release SET. The current value of order 1 is displayed.

SP1 and led OUT1 blink.

• 

Press UP or DOWN to increase or decrease the value.

• 

Press SET to confirm the new value. The actual value of order 2 will be displayed, 
SP2 and LED OUT2 blink.

• 

Press UP or DOWN to increase or decrease the value.

• 

Press SET to confirm the new value and exit.

Parameter setup

• Press SET for 8 seconds. Value 0 will blink.
• With UP and DOWN input the code (factory set as 0).
• Press SET to confirm the code. If correct, the label of the first parameter will be 

displayed.

• With UP or DOWN go to the desired parameter in the parameter list.
• Press SET to see the value.
• With UP or DOWN change the value to the new value as desired.
• Press SET to confirm and exit again to the parameter list. (Also to exit to the list 

without parameter modification.)

• Press SET + DOWN to exit setup or wait for 1 minute.

Resetting the keyboard code

You can setup to 0 the keyboard code switching the unit off and on while pressing
the SET key.

Buzzer disconnection

Pressing  SET  with  DOWN  turns  off  the  buzzer  alarm.  The  message  of  alarm
continue appearing in the display.

Reprogramming factory values (H0)

•Access to parameter H0 as explained in parameter setup.
•Value 0 will be displayed.
•Press SET for 8 seconds. Pro will be displayed if they have been setup correctly.
•Press SET + DOWN to exit setup or wait for 1 minute.

Description 

Factory value

SP1 

Set Point 1 

10.0

SP2 

Set Point 2 

10.0

r0 

Dependency SP1 - SP2

ind

r1 

Differential for SP1

1.0

r2 

Differential for SP2

1.0

r3 

Band differential 1.0

1.0

r4 

Lower value for SP1

-99.9

r5 

Lower value for SP2

-99.9

r6 

Higher value for SP1

99.9

r7 

Higher value for SP2

99.9

r8 

Regulation or operating mode

On1

A0 

Alarm differential

0.1

A1 

Maximum alarm probe 1

99.9

A2 

Maximum alarm probe 2

99.9

A3 

Minimum alarm probe 1

99.9

A4 

Minimum alarm probe 2

99.9

A5 

Alarm verification time

18.0

A6 

Alarm probe 1 selection

AHL

A7 

Alarm probe 2 selection

AHL

c0 

Minimum relay stop time

0

c1 

Operation relay 1

dir

c2 

Operation relay 2

dir

c3 

Default operation relay 1

Opn

c4 

Default operation relay 2

Opn

P0 

Temperature scale selection

ºC

P1 

Calibration of probe 1

0.0

P2 

Calibration of probe 2

0.0

P3 

Decimal point 

yes

P4 

Probe to be displayed

sd1

P5 

Number of probes

2

H0 

Reprogramming

0

H1 

Keyboard protection

no

H2 

Operation LED OUT1

dir

H3 

Operation LED OUT2

dir

H4 

Address for serial communication  0

H5 

Access code to parameters

0