List of  parameters

Description

Units

Range

SP1

Set Point 1

Degrees 

r4 to r6

SP2

Set Point 2 

Degrees

r5 to r7 

r0

Dependency SP1-SP2

Range

ind/dep

r1

Differential for SP1

Degrees

0.1 to 20.0           

r2

Differential for SP2

Degrees       

0.1 to 20.0

r3    

Band differential

Degrees

0.1 to 20.0

r4    

Lowest value for SP1

Degrees

-99.9 to r6

r5    

Lowest value for SP2

Degrees

-99.9 to r7

r6    

Highest value for SP1

Degrees 

r4 to 302  

r7    

Highest value for SP2

Degrees

r5 to 302  

r8    

Regulation or operating mode

Range

On1/On2/nEU 

A0   

Alarm differential

Degrees

0.1 to 20.0 

A1   

Maximum alarm probe 1 (1)

Degrees

0.1 to 99.9  

A2   

Maximum alarm probe 2 (2)

Degrees 

0.1 to 99.9 

A3   

Minimum alarm probe 1 (1)

Degrees 

0.1 to 99.9 

A4   

Minimum alarm probe 2 (2)

Degrees 

0.1 to 99.9   

A5   

Alarm verification time

h-m (*)

0.0 to 18.0

A6   

Alarm probe 1 selection

Range

AHL/Ano/AH/AL

A7   

Alarm probe 2 selection

Range

AHL/Ano/AH/AL

c0   

Minimum relay stop time

Minutes

0 to 240

c1   

Operation relay 1 

Range

dir/inv

c2   

Operation relay 2

Range

dir/inv

c3   

Default operation relay 1

Range

Opn/Clo

c4   

Default operation relay 2

Range

Opn/Clo 

P0   

Temperature scale selection

Range

ºC/ºF

P1   

Calibration of probe 1

Degrees

-20.0 to 20.0 

P2   

Calibration of probe 2

Degrees

-20.0 to 20.0 

P3   

Decimal point

Range

no/yes 

P4   

Probe to be displayed

Range

sd1/sd2

P5  

Number of probes 

Range  

1/2 

H0  

Reprogramming

Range

0

H1  

Keyboard protection

Range

no/yes

H2  

Operation LED OUT1

Range

dir/inv

H3  

Operation LED OUT2

Range

dir/inv

H4  

Address for serial communication

Numeric

0 to 999

H5  

Access code to parameters

Numeric

0 to 999 

(*)h-m are data in format XX.Y where XX are hours and Y tens of minutes.
(1)referred to set 1.
(2)referred to set 2.

Parameter descriptions
SP1 = 

Operation order of relay 1. Specifies the ON/OFF point of relay 1. Variable

between r4 and r6.

SP2 = 

Operation order of relay 2. Specifies the ON/OFF point of relay 2. Variable

between r5 and r7.

r0 = 

Dependency between SP1 and SP2. Only for mode ONOFF1

ind = order for relay 2, SP2.
dep = order for relay 2, SP1+SP2.

r1 = 

Differential or hysteresis for relay 1. Temperature differential between ON/OFF

of relay 1 in ON/OFF control.

r2 = 

Differential or hysteresis for relay 2. Temperature differential between ON/OFF

of relay 2 in ON/OFF control.

r3 = 

Band differential. Temperature differential between ON/OFF of relays 1 and 2

in neutral area control. For relay 1 it is added to SP1 and for relay 2 it is subtracted
from SP1.

r4 = 

Lowest value for SP1. 

r5 = 

Lowest value for SP2.

r6 = 

Highest value for SP1.

r7 = 

Highest value for SP2.

r8 = 

Regulation or operating mode. Selection of the operating mode.

A0= 

Alarm differential. It is the temperature differential between the alarm On and

Off cycle.

A1= 

Maximum alarm probe1.

A2 = 

Maximum alarm probe2.

Maximum alarm ON when probe 2 higher than SP2+A2
Maximum alarm OFF when probe 2 lower than SP2+A2-A0.

A3 = 

Minimum alarm probe1.

Minimum alarm ON when probe 1 lower than SP1-A3
Minimum alarm OFF when probe 1 higher than SP1-A3+A0.

A4 = 

Minimum alarm probe2.

Minimum alarm ON when probe 2 lower than SP2-A4
Minimum alarm OFF when probe 2 higher than SP2-A4+A0.

A5 = 

Alarm verification time. Time from the alarm event until it trips.

A6 = 

Alarm probe 1 selection.

AHL=Maximum and minimum alarm probe 1 enabled.
Ano=No alarms probe 1.
AH=Maximum alarm probe 1 enabled.
AL=Minimum alarm probe 1 enabled.

A7 = 

Alarm probe 2 selection.

AHL=Maximum and minimum alarm probe 2 enabled.
Ano=No alarms probe 2.
AH=Maximum alarm probe 2 enabled.
AL=Minimum alarm probe 2 enabled.

c0 = 

Minimum relay stop time. Minimum time from the disconnection of a relay until

it can be switched on again.

c1 = 

Operation relay 1. Selection between direct or reverse operation for relay 1.

c2 = 

Operation relay 2. Selection between direct or reverse operation for relay 2.

c3 = 

Default operation relay 1. In case of failure of probe 1:

oPn= relay 1 will remain open.
Clo= relay 1 will remain closed.

c4 = 

Default operation relay 2. In case of failure of probe 1 (for all modes excepting

ON OFF2) or in case of failure of probe 2 (for mode ON OFF2):

oPn= relay 2 will remain open.
Clo= relay 2 will remain closed.

P0 = 

Temperature scale selection.

P1 = 

Calibration of probe 1. Offset degrees to be added to probe 1.

P2 = 

Calibration of probe 2. Offset degrees to be added to probe 2.

P3 = 

Decimal point. If the displayed value of the probes is desired with decimals or

not.

P4 = 

Probe to be displayed. Probe always on the display. The other probe can be

seen pressing the keys SET+UP.

sd1= probe 1.
sd2= probe 2.

P5 = 

Number of probes. If P5=1, there is not ON OFF2 mode. If selected, it will

operate as ONOFF1.

H0 = 

Reprogramming. Parameter to reprogram the thermostat.

H1 =

Keyboard protection.

To change the sets, enter into parameter and exit again. The protection setting 
is momentarily released. It switches on again 1 minute after the last time a key 
was pressed.
Yes= Keyboard Protected. 
No=Keyboard non protected.

H2 = 

Operation of LED OUT1.

dir= 

On when relay 1 is ON.

inv= 

On when relay 1 is OFF.

H3 = 

Operation of LED OUT2.

dir= 

On when relay 2 is ON.

inv= 

On when relay 2 is OFF.

H4 = 

Serial communication address. Address for computer connection.

H5 = 

Parameter entry code. Factory set as 0.