May, 2013
Page 46 of 52
949-1194 Rev. 7
SPECIFICATIONS
Selectable Inputs:
Thermocouple, RTD, DC Voltage, or DC Current selectable.
Input Impedance:
Thermocouple = 3 megohms minimum.
RTD current = 200 μA.
Current = 10 ohms.
Voltage = 5000 ohms.
Sensor Break Protection:
De-energizes control output to protect system after customer
set time. (See
I n P t
in Secure Menu.)
Set Point Range:
Selectable (See Input Ranges Page 49).
Display:
Two 4 digit, 7 segment 0.56˝ high LEDs.
Control Action:
Reverse (usually heating), Direct (usually cooling) selectable.
Proportional Band:
1 to 9999°F, °C, or counts.
Reset Time (Integral):
Off or 0.1 to 99.9 minutes.
Rate Time (Derivative):
Off or 0.01 to 99.99 minutes.
Cycle Rate:
1 to 80 seconds.
On - Off Differential:
Adjustable 1°F, 1°C, or 1 count to full scale in 1°F, 1°C, or 1 count
steps.
Alarm On - Off Differential:
1°F, 1°C, or 1 count.
Fuzzy Percent:
0 to 100%.
Fuzzy Rate:
Off or 0.01 to 99.99 counts per second.
Fuzzy Band:
Off or 1 to 4000 °F, °C, or counts.
Accuracy:
±0.25% of span, ±1 least signifi cant digit.
Resolution:
1 degree or 0.1 degree, selectable.
Line Voltage Stability:
±0.05% over the supply voltage range.
Temperature Stability:
100 ppm /°C typical, 200 ppm /°C maximum.
Common Mode Rejection:
140 db minimum at 60 Hz.
Normal Mode Rejection:
65 db typical, 60 db at 60 Hz.
Isolation:
Relay and SSR outputs:
1500 Vac to all other inputs and outputs;
SP1 and SP2 Current outputs:
500 Vac to all other inputs and outputs, but not
isolated from each other;
SP1 and SP2 Switched Voltage outputs:
500 Vac to all other inputs and outputs, but
not isolated from each other.
24 VDC Loop Power:
500VAC to all inputs and outputs.
Supply Voltage:
100 to 240 Vac, nominal, +10 -15%, 50 to 400 Hz. single phase; 132 to
240 VDC, nominal, +10 -20%.
Loop Power Supply:
24 VDC @ 50 mA, regulated.
Power Consumption:
5VA maximum.
Operating Temperature:
-10 to +55°C (+14 to 131°F).
Storage Temperature:
-40 to +80°C (-40 to 176°F).
Humidity Conditions:
0 to 90% up to 40°C non-condensing, 10 to 50% at 55°C
non-condensing.
Memory Backup:
Nonvolatile memory. No batteries required.
www.