May, 2013
Page 34 of 52
949-1194 Rev. 7
If
O u t 1
(Page 19) is set for # #
t P
, #
P U L
, or
P r o P
, then
S 1 O L
and
S 1 O H
appear. If
O u t 1
is set
for
O n O F
, then skip to
S 1 r E
.
S 1 O L
Set Point Output Low Limit: Select
0
to
1 0 0
% but not greater than
S 1 O H
. This
item limits the lowest output value. This is useful for adding a bias to the process
when needed. Factory set to
0
for output codes 1 and 3. Factory set to
2 0
for
output code 5 (20% output equals 4 mA output).
S 1 O H
Set Point 1 Output High Limit: Select
0
to
1 0 0
% but not less than
S 1 O L
for output
codes 1 and 3. Select
0
to
1 0 2
% but not less than
S 1 O L
for output code 5. This
item allows setting the maximum output limit. This is useful with processes that
are over powered. Adjustment to 102% allows setting current output to force a full
on condition for output devices which do not have bias adjustments. Factory set
to
1 0 0
for all output codes.
If
O u t 1
is set for # #
t P
, #
P U L
, or
P r o P
, then skip to
S 1 L P
(next page).
If
O u t 1
is set to
O n O F
(in the Secondary Menu), then the next three menu items can make
the
S P 1
and
S P 1 d
settings act like a high or low alarm set point. See the information on
alarm settings and the cautions and warnings
that apply to them on Pages 36-37.
Note that when Set Point 1 Power Interrupt ,
S 1 P i
is
O n
, and Set Point 1 Reset,
S 1 r E
, is
programmed to
H o L d
, the SP1 output will automatically reset upon a power failure and
subsequent restoration, if the process is below
S P 1
.
S 1 r E
Set Point 1 Reset. Select
O n O F
or
H o L d
.
O n O F
Output will automatically reset when process passes back through
S P 1 d
.
H o L d
Manual Reset. Reset (acknowledge) by simultaneously pressing the
INDEX
&
DOWN ARROW
keys for 3 seconds.
S 1 P i
Set Point 1 Power Interrupt. Select
O n
or
O F F
.
O n
Alarm Power Interrupt is
O n
. Output will automatically reset on
power-up if no alarm condition exists.
O F F
Alarm Power Interrupt is
O F F
. Output will be in the alarm condition on
power-up regardless of condition of process.
S 1 i H
Set Point 1 Inhibit: Select
O n
or
O F F
.
O n
Alarm Inhibit is
O n
. Alarm action is suspended until the process value
first enters a non-alarm condition.
O F F
Alarm Inhibit is
O F F
.
S 1 L P
Set Point Lamp: Select
O o n
or
O o F F
.
O o n
Lamp ON when Output is ON.
O o F F
Lamp OFF when Output is ON.