Page 30 of 52
949-1194 Rev. 7
I n P C
Input Correction: Select
- 5 0 0
to
0
to
5 0 0
°F, °C, or counts. This feature allows
the input value to be changed to agree with an external reference or to
compensate for sensor error.
Note:
I n P C
is reset to zero when the input type is
changed, or when decimal position is changed. Factory default is
0
.
F i L t
Digital Filter: Select
O F F
,
1
to
9 9
. In some cases the time constant of the sensor,
or noise, could cause the display to jump enough to be unreadable. A setting of 2
is usually sufficient filtering (2 represents approximately a 1 second time
constant). When the 0.1 degree resolution is selected this should be increased to
4. If this value is set too high, controllability will suffer.
L P b r
Loop Break Protection: Select
O F F
,
1
to
9 9 9 9
seconds. If, during operation, the
output is minimum (0%) or maximum (100%), and the input moves less than 5°F
(3°C) or 5 counts over the time set for
L P b r
, the
L O O P b A d
message will appear.
This condition can also be routed to an Alarm Condition if alarms are present and
turned On (see
A L b r
in the Secure Menu). The loop break error can be reset by
pressing the
ENTER
key when at the
L P b r
menu item. The
INDEX
&
ENTER
keys may also be used.
P O L
(Option 934, 936, Analog Retransmission Output) Process Output Low: Select -
450°F, -260°C, or -1999 counts to any value less than
P O H
.
P O H
(Option 934, 936, Analog Retransmission Output) Process Output High: Select
from any value greater than
P O L
to +9999°F, +5530°C, or 9999 counts.
P O S r
(Option 934, 936, Analog Retransmission Output) Process Output Source: Select
I n P
or
S P t
.
I n P
Output follows the Process Variable (input).
S P t
Output follows the Set Variable.
r S P t
(Option 924, 926, 928, Analog Remote Set Point) Remote Set Point: Select
O n
or
O F F
.
O F F
The control uses the value set for
S P 1
.
O n
The control uses the value set by the analog remote set point signal as
established by the Secure Menu items
r S C L
and
r S C H
. If the analog
signal fails, the control will display the error message
C H E C r S P t
and
revert to the
S P 1
local value.