
Doc: I456GB06_16.docx 29/06/2016
p. 6 / 20
Protections
The ADXL is equipped with a set of integrated protections to safeguard both the starter and the motor.
Some of these are configurable. Their settings are to found in the P04 Protections menu.
The following table summarises the available protections, and their parameters/alarms:
PROTECTION
MOTOR / STARTER PARAMETERS
ALARMS
COMMANDS
Three-phase line absent
MOTOR
-
A01 -
No phase
MOTOR
-
A02 -
Phase sequence
MOTOR
P04.11
A03 -
Frequency out of bounds
MOTOR
-
A04 -
Auxiliary voltage fault
MOTOR-STARTER
-
A05 -
Current asymmetry
MOTOR
P04.16 – P04.17
A06 -
Overcurrent MOTOR-STARTER
-
A07 -
Rotor jammed
MOTOR-STARTER
-
A08 -
Load too low (dry running, minimum torque)
MOTOR
P04.08 – P04.09
A09 -
Starting time too long
MOTOR
P04.10
A10 -
Bypass relay fault
STARTER
-
A11 -
Motor thermal protection pre-alarm
MOTOR
-
A12 -
Starter thermal protection pre-alarm
STARTER
-
A13 -
Motor thermal protection
MOTOR
P04.01-P04.02-P04.03- P04.04 – P04.05
A14 C02
Phases shorted
STARTER
-
A16 – A17 -
Temperature sensor fault
STARTER
-
A18 -
Line voltage too low
MOTOR
P04.12 – P04.13
A19 -
Line voltage too high
MOTOR
P04.14 – P04.15
A20 -
Maintenance interval
MOTOR-STARTER
P04.18
A22 C01
Fan fault / fans jammed
STARTER
-
A23-A24 -
Motor thermal protection
The ADXL is equipped with an electronic motor thermal protection, which can be configured in menu
P04 Protections
.
The display shows the thermal status of the motor both numerically and graphically, and by convention displays 100% when the motor is running stably at nominal voltage and current
(100%).
When the current is >112%In (In = motor nominal current) the thermal status increases to its maximum value, which is 140%, and trips alarm
A14 Motor thermal protection
.
The trip time is shown in the tables given below as a function of the overload current. The curves for the various graphs refer to the curve selected with parameters P04.02 and P04.03.
The cold trip curves indicate the trip time starting from thermal status 0%, while the hot trip curves start from thermal status 100%.
With the motor stopped, the thermal status will tend to zero in a set time which depends on the configured class of thermal protection.
The motor thermal protection alarm can be reset when the thermal status falls to or below the value of
P04.04 Motor thermal protection reset
, which has a default value of 120%. This
value can be modified for specific needs, without changing the trip time in any way.
The motor's thermal status updates correctly even if there is no auxiliary supply to the control board.
Cold trip curves Hot trip curves
Motor thermal protection via PTC
The ADXL's IN3 input can be configured to connect to a PTC motor thermal protection sensor.
The trip and reset values are conforming with DIN 44081.
Tripping the sensor initiates the alarm
A14 Motor thermal protection
and stops the motor.
The alarm can only be reset when the PTC sensor's resistance returns within the values defined by the standard.
Starter thermal protection
The display shows the numerical temperature of the heatsink/thyristors and graphically shows the thermal status of the starter.
When the graphic bar reaches its maximum value, it trips the alarm
A15 Starter thermal protection
.
The alarm resets automatically when the starter returns to an acceptable temperature.
t
1000
100
10
1
Class 40
Class 35
Class 30
Class 25
1
Class
0.
%
10
20
30
40
50
60
70
t
1000
100
10
1
Class 40
Class 35
Class 30
Class 25
1
Class 2
0.1
%
20
30
40
50
60
70